B.2 Parameter Table
H1-
Function
Setting
Reverse Run Command (2-Wire
41
sequence)
61
External Search Command 1
62
External Search Command 2
67
Communications Test Mode
No.
Name
Use H2 parameters to assign functions to the multi-function digital output MA-MB-MC.
Terminal MA, MB
H2-01
and MC Function
Selection (relay)
H2-01
Function
Setting
0
During Run
1
Zero Speed
2
Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
B
Torque Detection 1 (N.O.)
E
Fault
F
Not used
10
Minor Fault
17
Torque Detection 1 (N.C.)
1A
Reverse Direction
1E
Restart Enabled
3C
LOCAL/REMOTE Status
3D
Speed Search
100 to 102;
104 to 108;
10B, 10E,
H2 Parameter Functions Reversed
110, 117,
Output Switching of 0 to 13D
11A, 11E,
13C, 13D
No.
Name
Terminal A1
H3-01
Signal Level
Selection
H3-03
Terminal A1 Gain
<22>
Setting
H3-04
Terminal A1 Bias
<22>
Setting
H3-13 Analog Input Filter
Time Constant
<22> Parameter can be changed during run.
176
H1 Multi-Function Digital Input Selections
Open: Stop
Closed: Reverse run
Closed: Activates Current Detection Speed Search from the max. output
frequency (E1-04)
Closed: Activates Current Detection Speed Search from the frequency reference
Tests the MEMOBUS/Modbus RS-422/485 interface.
Description
H2: Multi-Function Digital Output MA-MB-MC
Refer to H2 Multi-Function Digital Output Settings on page
for a description of setting values.
H2 Multi-Function Digital Output Settings
Closed: A Run command is active or voltage is output
Closed: Output frequency is 0
Closed: Output frequency equals the speed reference (plus or minus 2 Hz
hysteresis)
Closed: Output frequency is less than or equal to the value in L4-01 with 2 Hz
hysteresis
Closed: Output frequency is greater than the value in L4-01 with 2 Hz hysteresis
Closed: Drive Ready. The drive is powered up, not in a fault state, and in the
Drive mode
Closed: DC bus voltage is below the Uv trip level
Closed: There is no output voltage
Closed: Output current/torque exceeds the torque value set in parameter L6-02
for longer than the time set in parameter L6-03
Closed: Fault occurred (other than CPF00 and CPF01)
Set this value when the terminal is not used, or when using the terminal in the
pass-through mode
Closed: An alarm is triggered
Open: When the output current exceeds the value set in parameter L6-02 for
more time than is set in parameter L6-03
Closed: Drive is running in the reverse direction
Closed: An automatic restart is performed
Closed: LOCAL
Open: REMOTE
Closed: Speed search is being executed
Reverse the output switching of the multi-function output functions. Set the last
two digits of 1 to reverse the output signal of that specific function
Examples:
Setting "108" reverses the output of "During baseblock", which is setting value
08
Setting "13C" reverses the output of "LOCAL/REMOTE Status", which is
setting "3C"
Description
Use H3 parameters to set the analog input terminal A1.
Sets the input level for terminal A1.
0: 0 to +10 V (lower limit)
1: 0 to +10 V (no lower limit)
2: 4 to 20 mA
3: 0 to 20 mA
Sets the level of the input value when 10 V (20 mA) is input at
terminal A1.
Sets the level of the input value when 0 V (0 or 4 mA) is input at
terminal A1.
Sets the primary delay filter time constant for terminal A1 or
potentiometer (optional). Used for noise filtering.
Description
176
Description
H3: Analog Input A1
Range
Def.
Mode
0 to 13D
E
O
Range
Def.
Mode
0 to 3
0
O
-999.9 to
100.0%
O
999.9
-999.9 to
0.0%
O
999.9
0.00 to 2.00 0.03 s
O
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Page
94
94
94
95
Addr.
Pg.
Hex
40B
95
Page
95
95
96
96
96
97
97
97
97
97
97
97
97
98
98
98
98
98
Addr.
Pg.
Hex
410
98
411
99
412
99
41B
101

Advertisement

Table of Contents
loading

Table of Contents