Control Circuit

Type
No.
Signal name
Input power supply
PCS
Internal 24 VDC
P24
Multi-function Input selection 1
1
Digital
Multi-function Input selection 2
input
2
signals
Multi-function Input selection 3
3
Multi-function Input selection 4
4
Multi-function Input selection 5
5
Multi-function Input selection common
L
Frequency reference power supply
H
Voltage frequency reference signal
O
Current frequency reference signal
OI
Frequency reference common
L
NC output
AL2
NO output
AL1
Relay Output common
AL0
Multi-function output terminal
11
Output signal common
CM2
Analog frequency monitor/Analog output
AM
current monitor

Side by side mounting

JX
Function
External power supply terminal for input signal (input)
...At sink logic
Internal power supply output terminal for input signal (output)
...At source logic
24 VDC internal power supply
Factory setting: Forward/ Stop
Factory setting: Reverse/ Stop
Factory setting: Fault reset
Factory setting: Emergency stop fault
Factory setting: Multi-step speed reference 1
--
10 VDC 10 mA max
0 to 10 VDC (10 KΩ)
4 to 20 mA (250 Ω)
--
Factory default relay settings
Under normal operation:
Under abnormal operation or power shutdown: AL1-AL0 Open
Factory setting: Frequency arrival signal at a constant speed
--
Factory setting: Analog frequency monitor
Signal level
24 VDC ±10%
24 VDC ±10% 30 mA
--
250 VAC 2.5 A
30 VDC 3 A
AL2-AL0 Closed
250 VAC 1 A
30 VDC 1 A
27 VDC
50 mA max
0 to 10 VDC 1 mA