Fins Protection Tab Page (Single Cpu Systems Only) - Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual

Cs1d duplex system
Table of Contents

Advertisement

Specific PLC Setup Settings
6-2-9

FINS Protection Tab Page (Single CPU Systems Only)

Enabling FINS Write Protection (Use FINS Write Protection)
Address in
Programming
Console
Word
Bit(s)
448
15
0: Disable FINS
write protection
1: Enable FINS write
protection
Default: 0
Nodes Excluded from Write Protection (Protection Releasing Addresses)
Address in
Programming
Console
Word
Bit(s)
Set the nodes and networks from which FINS write operations will be enabled. The total number of nodes set to be
excluded from write protection will be automatically set.
A maximum of 32 nodes can be set. If these settings are not made (i.e., if the total number of nodes is 0), write operations
will be disabled for all nodes but the local node.
Note: This setting is valid only when FINS write protection has been enabled.
449 to
8 to 15
0 to 127
480
(00 to 7F hex)
0 to 7
1 to 255
(01 to FE hex)
Note: 255 (FF hex)
can be set to include
all nodes in the
specified network.
448
0 to 7
0 to 32
(00 to 20 hex)
Settings
Enables or disables write protection for the
CPU Unit from FINS command sent over a
network (i.e., all connections except for
serial connections).
Note This setting cannot be used with Duplex CPU Systems.
Settings
FINS command source network address
FINS command source node address
Number of nodes excluded from protection
(Automatically calculated by the CX-Pro-
grammer; do not set.)
Note This setting cannot be used with Duplex CPU Systems.
Function
Function
Section 6-2
Related
New set-
flags and
ting's effec-
words
tiveness
---
At any time
Related
New set-
flags and
ting's effec-
words
tiveness
---
At any time
---
---