Startup Settings and Maintenance
Confirming the User Program Date
Auxiliary Area Words
6-6-8
Write-protection from FINS Commands Sent to CPU Units via
Networks
Computer #1
330
The dates the program and parameters were created can be confirmed by
checking the contents of A090 to A097.
Note The CS1G/H-CPU@@ (-V1) and CJ1@-CPU@@ CPU Units do not support
this function.
Name
User Program
A090 to
Date
A093
Parameter Date A094 to
A097
For CS/CJ-series CPU Units Ver. 2.0 or later, protection can be set to prevent
writing to and otherwise controlling CPU Units by using FINS commands via
networks (i.e., connections other than direct serial connections). This includes
writing from applications using FinsGateway as well as from the CX-Program-
mer, CX-Protocol, and CX-Process. Reading will still be possible in this case.
The following operations will be prohibited if write-protection is set: Download-
ing the user program, PLC Setup, I/O memory, or other data; changing the
operating mode; online editing; and any other write or control operations.
Even if write-protection is set, specific nodes can be set as exception to
enable executing write/control operations from them.
Protected against being written
by FINS commands sent from
nodes on networks, e.g., cannot
be written from computer #1,
Disabled
PLC #1, or PLC #2.
Disabled
PLC #1
Network
Address
The time and date the user program was last over-
written in memory is given in BCD.
A09000 to A09007
A09008 to A09015
A09100 to A09107
A09108 to A09115
A09200 to A09207
A09208 to A09215
A09300 to A09307
The time and date the parameters were last overwrit-
ten in memory is given in BCD. The format is the
same as that for the User Program Date given above.
Network
Disabled
PLC #2
Network
Write-access set for
this PLC.
Section 6-6
Description
Seconds (00 to 59 BCD)
Minutes (00 to 59 BCD)
Hour (00 to 23 BCD)
Day of month (01 to 31 BCD)
Month (01 to 12 BCD)
Year (00 to 99 BCD)
Day (00 to 06 BCD)
Day of the week:
00: Sunday, 01: Monday,
02: Tuesday, 03: Wednesday,
04: Thursday, 05: Friday,
06: Saturday
Enabled
Enabled
Disabled
PLC #3
Computer #2
Exceptions are set to enable
writing using FINS commands
from specific nodes, e.g., PLC
#3 and computer #2.