FINS Commands
Parameters
Comments
204
Program number (command)
Always FFFF (hex).
End code (response)
Refer to 5-1-3 End Codes for information on end codes.
Even if any other device has the access right, the access right can be
acquired with this command and a normal end code will be returned.
When ACCESS RIGHT FORCED ACQUIRE (command code 0C02) is exe-
cuted while any other device has the access right, subsequent commands
cannot be executed from the other device. This command should generally
not be used during normal processing.
The following table shows which FINS commands can be executed even
when another device holds the access right.
Command
code
0101
MEMORY AREA READ
0102
MEMORY AREA WRITE
0103
MEMORY AREA FILL
0104
MULTIPLE MEMORY AREA READ
0105
MEMORY AREA TRANSFER
0201
PARAMETER AREA READ
0202
PARAMETER AREA WRITE
0203
PARAMETER AREA CLEAR
0306
PROGRAM AREA READ
0307
PROGRAM AREA WRITE
0308
PROGRAM AREA CLEAR
0401
RUN
0402
STOP
0501
CPU UNIT DATA READ
0502
CONNECTION DATA READ
0601
CPU UNIT STATUS READ
0620
CYCLE TIME READ
0701
CLOCK READ
0702
CLOCK WRITE
0920
MESSAGE CLEAR
0C01
ACCESS RIGHT ACQUIRE
0C02
ACCESS RIGHT FORCED ACQUIRE
0C03
ACCESS RIGHT RELEASE
2101
ERROR CLEAR
2102
ERROR LOG READ
2103
ERROR LOG CLEAR
2140
FINS WRITE ACCESS LOG READ
2141
FINS WRITE ACCESS LOG CLEAR
2201
FILE NAME READ
2202
SINGLE FILE READ
2203
SINGLE FILE WRITE
2204
FILE MEMORY FORMAT
2205
FILE DELETE
2207
FILE COPY
2208
FILE NAME CHANGE
Command name
Section 5-3
Command execution
while another device
has access right
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
No
No
No
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
No
Yes
No
Yes
No
Yes
Yes
No
No
No
No
No