[1-1]=
shows the status of low noise operation.
1=unit is currently operating under low
noise restrictions
0=unit is currently not operating under low
noise restrictions
Low noise operation reduces the sound
generated by the unit compared to nominal
operating conditions.
Low noise operation can be set in mode 2.
There are two methods to activate low noise
operation of the outdoor unit system.
The first method is to enable an automatic low
noise operation during night time by field
setting. The unit will operate at the selected low
noise level during the selected time frames.
The second method is to enable low noise
operation based on an external input. For this
operation an optional accessory is required.
[1-2]=
shows the status of power consumption
limitation operation.
1=unit is currently operating under power
consumption limitation
0=unit is currently not operating under
power consumption limitations
Power consumption limitation reduces the
power consumption of the unit compared to
nominal operating conditions.
Power consumption limitation can be set in
mode 2. There are two methods to activate
power consumption limitation of the outdoor
unit system.
The first method is to enable a forced power
consumption limitation by field setting.
The unit will always operate at the selected
power consumption limitation.
The second method is to enable power
consumption limitation based on an external
input. For this operation an optional accessory
is required.
[1-5]=
shows the current T
See "15.3 Energy saving and optimum
operation" for more details about the
contents of this value
[1-6]=
shows the current T
See "15.3 Energy saving and optimum
operation" for more details about the
contents of this value
48
01_EN_3P748230-1.indd 48
target parameter position.
e
target parameter position.
c
[1-10]=
shows the total number of connected indoor
units.
It can be convenient to check if the total
number of indoor units which are installed
match the total number of indoor units which
are recognized by the system. In case there
is a mismatch, it is advised to check the
communication wiring path between outdoor
and indoor units (F1/F2 communication line).
See "12.5.1 Transmission wiring route".
[1-13]=
shows the total number of connected outdoor
units (in case of multiple outdoor system).
It can be convenient to check if the total
number of outdoor units which are installed
matches the total number of outdoor units
which are recognized by the system. In case
there is a mismatch, it is advised to check the
communication wiring path between outdoor
and outdoor units (Q1/Q2 communication line).
See "12.5.1 Transmission wiring route".
[1-17]=
shows the latest malfunction code.
[1-18]=
shows the malfunction code which occurred
1 time before current malfunction code.
[1-19]=
shows the malfunction code which occurred
2 time before current malfunction code.
When the latest malfunction codes were
reset by accident on an indoor unit user
interface, they can be checked again through
this monitoring settings. For the content or
reason behind the malfunction code see
"16.2 Malfunction code list", where most
relevant malfunction codes are explained.
Detailed information about malfunction codes
can be consulted in the service manual of
this unit.
[1-38]=
shows the number of Mini-split indoor units
connected to the system.
[1-40]=
shows the current cooling comfort setting.
See "15.3 Energy saving and optimum
operation" for more details about this setting.
[1-41]=
shows the current heating comfort setting.
See "15.3 Energy saving and optimum
operation" for more details about this setting.