14.3 Method for adding refrigerant

14.3.1 Flow chart
Location of valves for A, B
A
B
C
No
Step 4AB
• Open valve B to field piping via
liquid stop valve
• Execute pre-charging amount: Q (kg)
• Close valve B if no additional
refrigerant can be charged
• Q Should be 50% (±10%) of R
* if [R-(6 x n)] > R/2.
Then Q'(kg) can be calculate refer
formula below.
Q'=R-(6 x n)
When Q' = Refrigerant pre-charging
amount (kg)
n = number of the outdoor units
A (Automatic refrigerant charge with test run)
Step 5A
• Automatic refrigerant charge with test run
procedure
Step 6A
• Activate field setting [2-3]=2*
• Test run will be started with auto charge
operation
* See 15. Monitoring function and
field settings.
Cooling charging
(" t01 " flashing: pressure equalization)
(" t02 " flashing: starting control)
(" t03 " flashing: waiting for stable cooling)
(" t05 " flashing: auto charging operation)
During " t01 " to " t05 " is flashing.
• Push BS2 more than 5 seconds within
3 minutes.
• Open valve C.
The currently displayed number will stop
flashing.
Refrigerant will be charged, and test run
will be continued automatically after
" t05 " operated.
Test run finished = " t10 " is flashing.
• Close valve C.
• Push BS1 to leave program.
• Charging is finished.
• Fill in the amount on the additional
refrigerant charge label.
Finished
See figure "Location of valves" ; for more information, refer to the following detail in this chapter.
42
01_EN_3P748230-1.indd 42
Step 1
• Calculate additional refrigerant charge
amount: R (kg)
(see "14.2 Calculating the additional
refrigerant charge").
Step 2
• Select additional refrigerant charge
function
A/B (Automatic refrigerant charge)
Step 3AB
Refrigerant overcharge happened
• Recover refrigerant to reach R=Q
R ≤ 4 kg
• Go to step 5Ca
Yes
B (Automatic refrigerant charge)
Step 5B
• Automatic refrigerant charge
procedure
Step 6B
• Push 1 x BS2: " 888 "
• Push BS2 for more than
5 seconds
Cooling charging
(" t01 " pressure equalization)
(" t02 " starting control)
(" t03 " waiting for stable cooling)
" t03 " is flashing.
• Push BS2 within 5 minutes.
• Open valve C
Display show " t03 " and low
pressure valve with an interval of
1 second.
Refrigerant will be charged
automatically
" pe " = charging nearly finished "
p9 " = charging finished
or
P (kg) was added during
auto charge
R=Q+P
• Close valve C
• Push BS1 to leave program
• Charging is finished
• Fill in the amount on the
additional refrigerant charge label
• Go to test run (see "16.1 Test
operation")
Finished
Location of valves for C
A
B
C (Manual refrigerant charge)
Step 3C+4C
R<Q
• Open valve B to field piping via
liquid stop valve
• Execute pre-charging amount:
Q (kg)
• Close valve B if no additional
refrigerant can be charged
R>Q
Step 5Cb+6C
Manual refrigerant charging
method (in cooling operation)
Step 7C
Activate field setting [2-20]=1
Unit will start manual refrigerant
charging operation.
• Open valve A
• Charge remaining amount of
refrigerant P (kg)
R=Q+P
• Close valve A
• Push BS3 to stop manual
charging
• Charging is finished
• Fill in the amount on the
additional refrigerant charge label
• Go to test run
(see "16.1 Test operation").
Finished
Step 5Ca
R=Q
• Close valve B
• Charging is finished
• Fill in the amount on the
additional refrigerant charge
label
• Go to test run
(see "16.1 Test operation").
Finished