Voltage Planar Fault Is Displayed In The Event Log; Unusual Smell; Server Seems To Be Running Hot; Cannot Enter Legacy Mode After Installing A New Adapter - Lenovo ThinkSystem SD550 V3 User Manual

Hide thumbs Also See for ThinkSystem SD550 V3:
Table of Contents

Advertisement

• The server restarts automatically and attempts POST again.
• The server hangs, and you must manually restart the server for the server to attempt POST again.
After a specified number of consecutive attempts (automatic or manual), the server reverts to the default
UEFI configuration and starts System Setup so that you can make the necessary corrections to the
configuration and restart the server. If the server is unable to successfully complete POST with the default
configuration, there might be a problem with the system board (system board assembly). You can specify the
number of consecutive restart attempts in System Setup. Click System Settings ➙ Recovery ➙ POST
Attempts ➙ POST Attempts Limit. Available options are 3, 6, 9, and 255.

Voltage planar fault is displayed in the event log

Complete the following steps until the problem is solved.
1. Revert the system to the minimum configuration. See
minimally required number of processors and DIMMs.
2. Restart the system.
• If the system restarts, add each of the removed items one at a time and restart the system each time
until the error occurs. Replace the item for which the error occurs.
• If the system does not restart, suspect the system board (system board assembly).

Unusual smell

Complete the following steps until the problem is solved.
1. An unusual smell might be coming from newly installed equipment.
2. If the problem remains, contact Lenovo Support.

Server seems to be running hot

Complete the following steps until the problem is solved.
Multiple compute nodes or chassis:
1. Make sure that the room temperature is within the specified range (see
management" on page
2. Make sure that the fans are installed correctly.
3. Update the UEFI and XCC firmware to the latest versions.
4. Make sure that the fillers in the server are installed correctly (see
procedures" on page 43
5. Use the IPMI command to ramp up the fan speed to the full fan speed to see whether the issue can be
resolved.
Note: The IPMI raw command should only be used by trained technician and the each system has its
own specific PMI raw command.
6. Check the management processor event log for rising temperature events. If there are no events, the
compute node is running within normal operating temperatures. Note that you can expect some
variation in temperature.

Cannot enter legacy mode after installing a new adapter

Complete the following procedure to solve the problem.
1. Go to UEFI Setup ➙ Devices and I/O Ports ➙ Set Option ROM Execution Order.
2. Move the RAID adapter with operation system installed to the top of the list.
3. Select Save.
13).
for detailed installation procedures).
"Node technical specifications" on page 6
"Ambient temperature
Chapter 5 "Hardware replacement
Chapter 8
for the
.
Problem determination
271