Lenovo 7D7M Reference

Messages and codes reference

Advertisement

Quick Links

ThinkSystem SD650 V3 / ThinkSystem SD650-
I V3 Neptune DWC Trays and DW612S
Neptune DWC Enclosure
Messages and Codes Reference
Machine Types: 7D7M

Advertisement

Table of Contents
loading

Summary of Contents for Lenovo 7D7M

  • Page 1 ThinkSystem SD650 V3 / ThinkSystem SD650- I V3 Neptune DWC Trays and DW612S Neptune DWC Enclosure Messages and Codes Reference Machine Types: 7D7M...
  • Page 2 Before using this information and the product it supports, be sure to read and understand the safety information and the safety instructions, which are available at: https://pubs.lenovo.com/safety_documentation/ In addition, be sure that you are familiar with the terms and conditions of the Lenovo warranty for your server, which can be found at: http://datacentersupport.lenovo.com/warrantylookup First Edition (June 2022) ©...
  • Page 3: Table Of Contents

    Chapter 3. UEFI events ..129 Contacting Support ... . . 199 UEFI events organized by severity ..129 © Copyright Lenovo 2022...
  • Page 4 ThinkSystem SD650 V3 / ThinkSystem SD650-I V3 Neptune DWC Trays and DW612S Neptune DWC Enclosure Messages and Codes Reference...
  • Page 5: Chapter 1. Messages

    Lenovo XClarity Provisioning Manager (although these events are not stored in the event log). Use this section to view the events that can be generated by Lenovo XClarity Controller, UEFI, or the Lenovo XClarity Provisioning Manager. For each event, a user action is available to help you understand what must be done to resolve the issue.
  • Page 6 – CA. Cooling - Fans, blowers, mux cards, policies, chillers/refrigeration, water management units, water pumps, water filtration, air flow sensors, thermal monitors. – DA. Display - Graphics adapters, op panel, monitor/console (including front/back panel, control panel, LCD panel etc). – IO. I/O connectivity - PCI/USB hub, bridge, bus, risers, configuration settings, interconnect, keyboard, mouse, KVM.
  • Page 7 – SS. Service & Support - LEPT FFDC Collection. – SS. Systems Management - Service & Support. – TR. Time Reference - RTC, Master clock, drawer clocks, NTP. – UN. Unknown/any entity. – UP. LEPT Firmware Update. – UP. Systems Management - Updates. –...
  • Page 8 ThinkSystem SD650 V3 / ThinkSystem SD650-I V3 Neptune DWC Trays and DW612S Neptune DWC Enclosure Messages and Codes Reference...
  • Page 9: Chapter 2. Xclarity Controller Events

    Chapter 2. XClarity Controller events When a hardware event is detected by the Lenovo XClarity Controller on the server, the Lenovo XClarity Controller writes that event in the system-event log on the server. Notes: Event identifier (ID) is a unique identifier used to search for XCC events. The event message may have one or more arguments, which could be replaceable text of FRU name or sensor name to identify the failed component.
  • Page 10: Xcc Events That Automatically Notify Support

    If you have configured this function and this field is set to Yes, Lenovo Support will be notified automatically if the event is generated. While you wait for Lenovo Support to call, you can perform the recommended actions for the event.
  • Page 11: Xcc Events Organized By Severity

    Table 1. Events that automatically notify Support (continued) Message String Event ID FQXSPIO0015M Fault in slot [PhysicalConnectorSystemElementName] on system [ComputerSystemElementName]. FQXSPMA0007L Scrub Failure for [PhysicalMemoryElementName] on Subsystem [MemoryElementName]. FQXSPMA0008N Uncorrectable error detected for [PhysicalMemoryElementName] on Subsystem [MemoryElementName]. FQXSPMA0011G Memory Logging Limit Reached for [PhysicalMemoryElementName] on Subsystem [MemoryElementName].
  • Page 12 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPBT0007I No bootable media available for system Informational [ComputerSystemElementName]. FQXSPCA2002I Numeric sensor [NumericSensorElementName] going low (lower Informational critical) has deasserted. FQXSPCA2007I Numeric sensor [NumericSensorElementName] going high (upper Informational non-critical) has deasserted.
  • Page 13 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPEA2001I Sensor [SensorElementName] has deasserted the transition from Informational normal to non-critical state. FQXSPEA2002I Sensor [SensorElementName] has transitioned to a less severe state Informational from critical. FQXSPEA2003I Link up is detected on port [arg1] of the PCIe device [arg2]. Informational FQXSPEM0003I The Log [RecordLogElementName] has been cleared.
  • Page 14 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPEM4017I The RAID controller detected one or more possible configuration Informational changes within the subsystem. Please check the drive LED status. If necessary, contact technical support for additional assistance.([arg1], [arg2],[arg3],[arg4],[arg5]) FQXSPEM4018I Enclosure/Chassis issue detected with one or more units.
  • Page 15 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPFC4005I UEFI deployment boot mode has been disabled. Informational FQXSPFW0003I The System [ComputerSystemElementName] encountered firmware Informational progress. FQXSPIO0010I A Correctable Bus Error has occurred on bus [SensorElementName]. Informational FQXSPIO2003I System [ComputerSystemElementName] has recovered from a Informational...
  • Page 16 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPNM4009I IP address of default gateway modified from [arg1] to [arg2] by user Informational [arg3]. FQXSPNM4011I ENET[[arg1]] DHCP-HSTN=[arg2], DN=[arg3], IP@=[arg4], SN=[arg5], Informational GW@=[arg6], DNS1@=[arg7] . FQXSPNM4012I ENET[[arg1]] IP-Cfg:HstName=[arg2], IP@=[arg3] ,NetMsk=[arg4], Informational GW@=[arg5] .
  • Page 17 User [arg1] has set the SMTP Server reverse-path to [arg2]. Informational FQXSPNM4052I DHCP specified hostname is set to [arg1] by user [arg2]. Informational FQXSPNM4053I DNS discovery of Lenovo XClarity Administrator has been [arg1] by Informational user [arg2]. FQXSPNM4054I The hostname from DHCP is [arg1] by user [arg2]. Informational FQXSPNM4055I The hostname from DHCP is invalid.
  • Page 18 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPOS4009I OS Crash Video Captured. Informational FQXSPPP4000I Attempting to [arg1] server [arg2] by user [arg3]. Informational FQXSPPP4001I Server Power Off Delay set to [arg1] by user [arg2]. Informational FQXSPPP4002I Server [arg1] scheduled for [arg2] at [arg3] by user [arg4].
  • Page 19 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPPP4031I The server was power-cycled via Platform Event Filter. Informational FQXSPPP4032I The server was soft reset. Informational FQXSPPP4033I The server was powered up via Real Time Clock (scheduled power Informational on).
  • Page 20 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPPW2001I [PowerSupplyElementName] has been removed from container Informational [PhysicalPackageElementName]. FQXSPPW2002I [PowerSupplyElementName] has returned to OK status. Informational FQXSPPW2003I Failure no longer predicted on [PowerSupplyElementName]. Informational FQXSPPW2006I [PowerSupplyElementName] has returned to a Normal Input State. Informational FQXSPPW2008I [PowerSupplyElementName] has been turned on.
  • Page 21 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPSD2011I Failure no longer Predicted on drive [arg1] in the enclosure/chassis Informational (MTM-S/N: [arg2]). FQXSPSD2012I Hot Spare disabled for drive [arg1] in the enclosure/chassis (MTM-SN: Informational [arg2]). FQXSPSD2013I Array critical deasserted on drive [arg1] in the enclosure/chassis Informational (MTM-S/N: [arg2]).
  • Page 22 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPSE4018I User [arg1] removed. Informational FQXSPSE4019I User [arg1] password modified. Informational FQXSPSE4020I User [arg1] role set to [arg2]. Informational FQXSPSE4021I User [arg1] custom privileges set: [arg2][arg3][arg4][arg5][arg6][arg7] Informational [arg8][arg9]. FQXSPSE4022I User [arg1] for SNMPv3 set: AuthenticationProtocol=[arg2], Informational...
  • Page 23 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPSE4044I User [arg1] third-party hashed password has been [arg2] by user Informational [arg3] from [arg4] at IP address [arg5]. FQXSPSE4045I The Salt of user [arg1] third-party password has been [arg2] by user Informational [arg3] from [arg4] at IP address [arg5].
  • Page 24 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPUN0017I Sensor [SensorElementName] has transitioned to normal state. Informational FQXSPUN0026I Device [LogicalDeviceElementName] has been added. Informational FQXSPUN0048I The RAID controller in PCI slot [arg1] in optimal status. Informational FQXSPUN0056I Sensor [SensorElementName] has deasserted.
  • Page 25 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPNM4010I DHCP[[arg1]] failure, no IP address assigned. Warning Warning FQXSPNM4032I DHCPv6 failure, no IP address assigned. FQXSPPP4009I The measured power value exceeded the power cap value. Warning The new minimum power cap value exceeded the power cap value. Warning FQXSPPP4010I FQXSPPU0002G...
  • Page 26 Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPIO0003N A diagnostic interrupt has occurred on system Error [ComputerSystemElementName]. FQXSPIO0004L A bus timeout has occurred on bus [SensorElementName]. Error FQXSPIO0006N A software NMI has occurred on system Error [ComputerSystemElementName].
  • Page 27: List Of Xclarity Controller Events

    Table 2. Events organized by severity (continued) Message String Severity Event ID FQXSPSD0002L Drive [arg1] in the enclosure/chassis(MTM-SN: [arg2]) has a fault. Error Error FQXSPSD0005L Array [ComputerSystemElementName] is in critical condition. FQXSPSD0006L Array [ComputerSystemElementName] has failed. Error FQXSPSD0007L Array critical asserted on drive [arg1] in the enclosure/chassis (MTM- Error S/N: [arg2]).
  • Page 28 3. If problem persists, collect Service Data log. 4. Contact Lenovo Support. • FQXSPBR4002I: Management Controller [arg1] Reset was caused by restoring default values. This message is for the use case where a Management Controller has been reset due to a user restoring the configuration to default values.
  • Page 29 4. Disable the watchdog timer. 5. Check the integrity of the installed operating system. 6. If problem persists, collect Service Data log. 7. Contact Lenovo Support. • FQXSPBR4004I: Server timeouts set by user [arg1]: EnableOSWatchdog=[arg2], OSWatchdogTimout=[arg3], EnableLoaderWatchdog=[arg4], LoaderTimeout=[arg5]. A user configures Server Timeouts...
  • Page 30 1. Retry the operation. 2. AC cycle the system. 3. If Problem persists, collect Service Data log. 4. Contact Lenovo Support. • FQXSPBR4008I: Management Controller [arg1]: Configuration restoration from a file by user [arg2] failed to start. This message is for the use case where a user restores a Management Controller configuration from a file and the restoration fails to start.
  • Page 31 Complete the following steps: 1. Ensure fans are installed correctly. 2. If fan is installed with issue , please reinstall fan. 3. If the problem still exist, then please contact Lenovo support. • FQXSPCA0007J: Numeric sensor [NumericSensorElementName] going high (upper non-critical) has asserted.
  • Page 32 2. If the problem issue still exist, check XCC Web GUI to check the temporature value is still higher than system spec. 3. Please contact Lenovo support. • FQXSPCA0015J: Sensor [SensorElementName] has transitioned from normal to non-critical state. This message is for the use case when an implementation has detected a Sensor transitioned to non- critical from normal.
  • Page 33 1. Check the event log of XClarity Controller for any fan or cooling-related issues or power-related issues. 2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place,clean, and correctly installed. 3.
  • Page 34 Information only; no action is required • FQXSPCA2009I: Numeric sensor [NumericSensorElementName] going high (upper critical) has deasserted. This message is for the use case when an implementation has detected an Upper Critical sensor going high has deasserted. Severity: Info Serviceable: No Automatically notify Support: No Alert Category: Critical - Temperature SNMP Trap ID: 0...
  • Page 35 SNMP Trap ID: 0 CIM Prefix: PLAT CIM ID: 0523 User Action: Information only; no action is required • FQXSPCA2019I: Sensor [SensorElementName] has deasserted the transition to non-recoverable from a less severe state. This message is for the use case when an implementation has detected that the Sensor transition to non- recoverable from less severe has deasserted.
  • Page 36 SNMP Trap ID: CIM Prefix: IMM CIM ID: 0145 User Action: Information only; no action is required. • FQXSPCN4003I: Remote Control session started by user [arg1] in [arg2] mode has been closed. Remote Control session closed Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22...
  • Page 37 SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0142 User Action: Collect Service Data log and contact Lenovo Support. • FQXSPDM4003I: TKLM servers set by user [arg1]: TKLMServer1=[arg2] Port=[arg3], TKLMServer2= [arg4] Port=[arg5], TKLMServer3=[arg6] Port=[arg7], TKLMServer4=[arg8] Port=[arg9]. A user configured the TKLM servers...
  • Page 38 A user configured the TKLM device group Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0147 User Action: Information only; no action is required. • FQXSPDM4005I: User [arg1] has generated a new encryption key pair and installed a self-signed certificate for the TKLM client.
  • Page 39 Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0151 User Action: Information only; no action is required. • FQXSPDM4009I: User [arg1] has [arg2] file [arg3] from [arg4]. User has mounted/unmounted file from URL or server Severity: Info Serviceable: No Automatically notify Support: No...
  • Page 40 This message is for the use case when an implementation has detected that a Sensor has deasserted a transition to non-critical from normal. Severity: Info Serviceable: No Automatically notify Support: No Alert Category: Warning - Other SNMP Trap ID: 60 CIM Prefix: PLAT CIM ID: 0521 User Action: Use storcli or LSA to check if there is any warning or critical RAID event.
  • Page 41 This message is for the use case where a Management Controller Event Log on a system is 75% full. Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Event Log Fullness SNMP Trap ID: 35 CIM Prefix: IMM CIM ID: 0037 User Action: Information only;...
  • Page 42 Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0074 User Action: Information only; no action is required. • FQXSPEM4006I: Alert Configuration Global Event Notification set by user [arg1]: RetryLimit=[arg2], RetryInterval=[arg3], EntryInterval=[arg4]. A user changes the Global Event Notification settings. Severity: Info Serviceable: No Automatically notify Support: No...
  • Page 43 Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0152 User Action: Information only; no action is required. • FQXSPEM4010I: UEFI Reported: [arg1]. UEFI audit event logged. Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0161...
  • Page 44 SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0202 User Action: Information only; no action is required. • FQXSPEM4014I: The RAID controller has problem with the battery. Please contact technical support to resolve this issue.([arg1],[arg2],[arg3],[arg4],[arg5]) The RAID controller has problem with the battery Severity: Info Serviceable: No Automatically notify Support: Yes...
  • Page 45 Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0206 User Action: Information only; no action is required. • FQXSPEM4018I: Enclosure/Chassis issue detected with one or more units. Please check the enclosure/chassis units to repair the problem.([arg1],[arg2],[arg3],[arg4],[arg5]) Enclosure/Chassis issue detected with one or more units Severity: Info...
  • Page 46 Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0210 User Action: Information only; no action is required. • FQXSPEM4023I: One or more virtual drive are in abnormal status that may cause unavailable virtual drive.
  • Page 47 • FQXSPEM4026I: Drive error was detected by RAID controller. Please contact technical support to resolve this issue.([arg1],[arg2],[arg3],[arg4],[arg5]) Drive error was detected by RAID controller Severity: Info Serviceable: No Automatically notify Support: Yes Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0214 User Action: Information only;...
  • Page 48 • FQXSPEM4030I: A scheduled operation on the RAID controller has encountered an issue. Refer to RAID Logs under Server Management, Local Storage, for details.([arg1],[arg2],[arg3],[arg4],[arg5]) The RAID controller has scheduled operation issue Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0223 User Action:...
  • Page 49 UEFI deployment boot mode is enabled for NextBoot Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0197 User Action: Information only; no action is required. • FQXSPFC4004I: UEFI deployment boot mode is enabled for NextAc. UEFI deployment boot mode is enabled for NextAC Severity: Info Serviceable: No...
  • Page 50 3. Undo recent system changes (settings or devices added). Verify that the system boots. Then, re- install options one at a time to locate the problem. 4. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this error. Update UEFI firmware if applicable.
  • Page 51 CIM Prefix: PLAT CIM ID: 0224 User Action: Collect Service Data logs. Contact Lenovo Support. • FQXSPIO0006N: A software NMI has occurred on system [ComputerSystemElementName]. This message is for the use case when an implementation has detected a Software NMI.
  • Page 52 2. Check the event log of XClarity Controller for additional information about failing components. 3. If there are no entries related to the error in the event log, contact Lenovo support • FQXSPIO0013N: A Fatal Bus Error has occurred on bus [SensorElementName].
  • Page 53 2. Check the event log of XClarity Controller for additional information about failing components. Check http://support.lenovo.com/ for TECH tips or firmware updates that might correct the error. 3. If there are no entries related to the error in the event log, contact Lenovo support • FQXSPIO2003I: System [ComputerSystemElementName] has recovered from a diagnostic interrupt.
  • Page 54 Automatically notify Support: No Alert Category: Critical - Other SNMP Trap ID: 50 CIM Prefix: PLAT CIM ID: 0225 User Action: Information only; no action is required • FQXSPIO2006I: System [ComputerSystemElementName] has recovered from an NMI. This message is for the use case when an implementation has detected a Software NMI has been Recovered from.
  • Page 55 3. If the DIMMs have been upgraded just prior to the issue than update uEFI to the latest version. 4. If the problem persists, collect Service Data logs. 5. Contact Lenovo Support. • FQXSPMA0002N: Configuration Error for [PhysicalMemoryElementName] on Subsystem [MemoryElementName].
  • Page 56 3. If the DIMMs have been upgraded just prior to the issue than update uEFI to the latest version. 4. If the problem persists, collect Service Data logs. 5. Contact Lenovo Support. • FQXSPMA0007L: Scrub Failure for [PhysicalMemoryElementName] on Subsystem [MemoryElementName].
  • Page 57 3. If problem recurs on the same DIMM connector, replace the other DIMMs on the same memory channel. 4. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this memory error. 5. If problem recurs on the same DIMM connector, inspect connector for damage. If damage found or problem persists, collect Service Data log.
  • Page 58 3. If problem recurs on the same DIMM connector, replace the other DIMMs on the same memory channel. 4. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this memory error. 5. If problem recurs on the same DIMM connector, inspect connector for damage. If damage found or problem persists, collect Service Data log.
  • Page 59 SNMP Trap ID: CIM Prefix: PLAT CIM ID: 0508 User Action: Information only; no action is required • FQXSPMA2007I: Scrub Failure for [PhysicalMemoryElementName] on Subsystem [MemoryElementName] has recovered. This message is for the use case when an implementation has detected a Memory Scrub failure recovery. Severity: Info Serviceable: No Automatically notify Support: No...
  • Page 60 Alert Category: Warning - Memory SNMP Trap ID: CIM Prefix: PLAT CIM ID: 0509 User Action: Information only; no action is required • FQXSPNM4000I: Management Controller [arg1] Network Initialization Complete. This message is for the use case where a Management Controller network has completed initialization. Severity: Info Serviceable: No Automatically notify Support: No...
  • Page 61 User Action: Information only; no action is required. • FQXSPNM4004I: Ethernet locally administered MAC address modified from [arg1] to [arg2] by user [arg3]. This message is for the use case where a user modifies the Ethernet Port MAC address setting. Severity: Info Serviceable: No Automatically notify Support: No...
  • Page 62 2. Make sure that there is a DHCP server on the network that can assign an IP address to the XCC/ BMC. 3. If problem persists, collect Service Data log. 4. Contact Lenovo Support. • FQXSPNM4011I: ENET[[arg1]] DHCP-HSTN=[arg2], DN=[arg3], IP@=[arg4], SN=[arg5], GW@= [arg6], DNS1@=[arg7] .
  • Page 63 Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0022 User Action: Information only; no action is required. • FQXSPNM4012I: ENET[[arg1]] IP-Cfg:HstName=[arg2], IP@=[arg3] ,NetMsk=[arg4], GW@=[arg5] . This message is for the use case where a Management Controller IP address and configuration has been assigned statically using user data.
  • Page 64 Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0026 User Action: Information only; no action is required. • FQXSPNM4016I: Domain name set to [arg1] by user [arg2]. Domain name set by user Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none...
  • Page 65 CIM Prefix: IMM CIM ID: 0046 User Action: Information only; no action is required. • FQXSPNM4020I: IPv6 enabled by user [arg1] . IPv6 protocol is enabled by user Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0047 User Action: Information only;...
  • Page 66 Information only; no action is required. • FQXSPNM4024I: IPv6 stateless auto-configuration enabled by user [arg1]. IPv6 statless auto-assignment method is enabled by user Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0051 User Action: Information only;...
  • Page 67 IPv6 Link Local address is active Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0055 User Action: Information only; no action is required. • FQXSPNM4029I: ENET[[arg1]] IPv6-Static:HstName=[arg2], IP@=[arg3] ,Pref=[arg4], GW@=[arg5] . IPv6 Static address is active Severity: Info Serviceable: No...
  • Page 68 2. Make sure that there is a DHCPv6 server on the network that can assign an IP address to the XCC/ BMC. 3. If problem persists, collect Service Data log. 4. Contact Lenovo Support. • FQXSPNM4033I: Telnet port number changed from [arg1] to [arg2] by user [arg3]. A user has modified the telnet port number...
  • Page 69 Information only; no action is required. • FQXSPNM4036I: Web-HTTPS port number changed from [arg1] to [arg2] by user [arg3]. A user has modified the Web HTTPS port number Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0064 User Action: Information only;...
  • Page 70 A user has modified the SNMP Traps port number Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0068 User Action: Information only; no action is required. • FQXSPNM4041I: Syslog port number changed from [arg1] to [arg2] by user [arg3]. A user has modified the Syslog receiver port number Severity: Info Serviceable: No...
  • Page 71 Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0087 User Action: Information only; no action is required. • FQXSPNM4045I: DNS servers set by user [arg1]: UseAdditionalServers=[arg2], PreferredDNStype= [arg3], IPv4Server1=[arg4], IPv4Server2=[arg5], IPv4Server3=[arg6], IPv6Server1=[arg7], IPv6Server2=[arg8], IPv6Server3=[arg9]. A user configures the DNS servers Severity: Info Serviceable: No...
  • Page 72 Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0129 User Action: Information only; no action is required. • FQXSPNM4049I: User [arg1] has initiated a TKLM Server Connection Test to check connectivity to server [arg2]. User initiated a TKLM Server Connection test.
  • Page 73 SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0216 User Action: Information only; no action is required. • FQXSPNM4053I: DNS discovery of Lenovo XClarity Administrator has been [arg1] by user [arg2]. DNS discovery of Lenovo XClarity Administrator Severity: Info Serviceable: No...
  • Page 74 User Action: Information only; no action is required. • FQXSPNM4057I: Security: IP address: [arg1] had [arg2] login failures, it will be blocked to access for [arg3] minutes. This message is for the use case where IP address blocking. Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - IMM Network event...
  • Page 75 3. Reinstall the RNDIS or cdc_ether device driver for the operating system. 4. Disable the watchdog. 5. If problem persists, collect Service Data log. 6. Contact Lenovo Support.Check the integrity of the installed operating system. • FQXSPOS4004I: Operating System status has changed to [arg1]. Operating System status change...
  • Page 76 • FQXSPOS4005I: Host Power-On password changed by user [arg1] from [arg2] at IP address [arg3]. This message is for the use case where Host Power-On password changed. Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0231 User Action:...
  • Page 77 2. Check if the crash video recording is enabled 3. If problem persists, collect Service Data log. 4. Contact Lenovo Support. • FQXSPPP4000I: Attempting to [arg1] server [arg2] by user [arg3]. This message is for the use case where a user is using the Management Controller to perform a power function on the system.
  • Page 78 • FQXSPPP4002I: Server [arg1] scheduled for [arg2] at [arg3] by user [arg4]. A user configured a Server Power action at a specific time Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0082 User Action: Information only;...
  • Page 79 Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0114 User Action: Information only; no action is required. • FQXSPPP4007I: The maximum power cap value changed from [arg1] watts to [arg2] watts. Maximum Power Cap value changed Severity: Info Serviceable: No...
  • Page 80 Alert Category: Warning - Power SNMP Trap ID: 164 CIM Prefix: IMM CIM ID: 0118 User Action: Information only; no action is required. • FQXSPPP4011I: Power capping was activated by user [arg1]. Power capping activated by user Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID:...
  • Page 81 User Action: Information only; no action is required. • FQXSPPP4015I: Dynamic Power Savings mode has been turned on by user [arg1]. Dynamic Power Savings mode turned on by user Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0123 User Action:...
  • Page 82 • FQXSPPP4019I: Power cap throttling occurred. Power cap throttling occurrred Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0127 User Action: Information only; no action is required. • FQXSPPP4020I: The measured power value has returned below the power cap value. Power exceeded cap recovered Severity: Info Serviceable: No...
  • Page 83 Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0167 User Action: Information only; no action is required. • FQXSPPP4024I: The server was reset via push button. Server was reset via push button Severity: Info Serviceable: No...
  • Page 84 Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0171 User Action: Information only; no action is required. • FQXSPPP4028I: The server was automatically powered on because the power restore policy is set to always restore.. Server was automatically powered on because the power restore policy is set to always restore.
  • Page 85 Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0175 User Action: Information only; no action is required. • FQXSPPP4032I: The server was soft reset. Server was soft reset Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0176...
  • Page 86 User Action: Information only; no action is required. • FQXSPPP4036I: The server was powered off via push button. Server was powered off via push button Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0180 User Action: Information only;...
  • Page 87 Information only; no action is required. • FQXSPPP4040I: The server was powered off via Platform Event Filter. Server was power off via Platform Event Filter Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0184 User Action: Information only;...
  • Page 88 Management Controller reset was initiated by CMM Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0188 User Action: Information only; no action is required. • FQXSPPP4045I: Management Controller [arg1] reset was initiated by XCC firmware. Management Controller reset was initiated by XCC firmware Severity: Info Serviceable: No...
  • Page 89 Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0252 User Action: Information only; no action is required. • FQXSPPP4050I: Management Controller [arg1] reset was initiated to activate PFR Firmware. Management Controller reset was initiated to activate PFR Firmware. Severity: Info Serviceable: No Automatically notify Support: No...
  • Page 90 5. If the problem still exist and XCC event is realted to power supply unit, please upgrade power supply unit with supported specification. 6. Once you finish the action above and can't solve issue, please contact Lenovo support. • FQXSPPU0003N: [ProcessorElementName] has Failed with IERR.
  • Page 91 User Action: Complete the following steps: 1. If the system board or firmware was just updated, check the Lenovo support site for an applicable service bulletin or firmware update that applies to this processor error. 2. If problem persists, collect Service Data log.
  • Page 92 User Action: Complete the following steps: 1. Check Lenovo support site for an applicable service bulletin or UEFI firmware update that applies to this error. 2. Reboot system. 3. If problem persists, collect Service Data log. 4. Contact Lenovo Support.
  • Page 93 Severity: Error Serviceable: Yes Automatically notify Support: Yes Alert Category: Critical - Power SNMP Trap ID: 4 CIM Prefix: PLAT CIM ID: 0086 User Action: Please check event log in xClarity Controller (XCC) Web GUI to identify the power supply unit failure. Check system spec and replace the power supply unit to the same specification.
  • Page 94 This message is for the use case when an implementation has detected a Power Unit that has been Disabled. Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Power Off SNMP Trap ID: 23 CIM Prefix: PLAT CIM ID: 0106 User Action: Information only;...
  • Page 95 2. If the problem remains, collect Service Data logs. Contact Lenovo Support. 3. If the specified sensor is Planar 3.3V or Planar 5V, collect Service Data logs. Contact Lenovo Support. • FQXSPPW0057J: Sensor [SensorElementName] has transitioned from normal to non-critical state.
  • Page 96 2. If the error still present, remove A/C power and any recently installed components. 3. If the server successfully powers on, complete the following steps: a. Check the server proven website (http://www.lenovo.com/us/en/serverproven/index.shtml) to make sure that recently installed components are compatible with the server.
  • Page 97 Information only; no action is required • FQXSPPW2006I: [PowerSupplyElementName] has returned to a Normal Input State. This message is for the use case when an implementation has detected a Power Supply that has input that has returned to normal. Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other...
  • Page 98 CIM Prefix: PLAT CIM ID: 0481 User Action: Information only; no action is required • FQXSPPW2057I: Sensor [SensorElementName] has deasserted the transition from normal to non- critical state. This message is for the use case when an implementation has detected that a Sensor has deasserted a transition to non-critical from normal.
  • Page 99 CIM Prefix: PLAT CIM ID: 0164 User Action: Complete the following steps: 1. Check the Support Portal(http://support.lenovo.com/)for service bulletins and TECH tips and firmware update related to your drive. 2. Check for any other RAID-related error. 3. Replace the drive.
  • Page 100 CIM Prefix: PLAT CIM ID: 0164 User Action: Complete the following steps: 1. Check the Support Portal(http://support.lenovo.com/)for service bulletins and TECH tips and firmware update related to your drive. 2. Check for any other RAID-related error. 3. Replace the drive.
  • Page 101 • FQXSPSD0005I: Hot Spare enabled for drive [arg1] in the enclosure/chassis (MTM-SN: [arg2]). This message is for the use case when an implementation has detected a Hot Spare has been Enabled. Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: CIM Prefix: PLAT CIM ID: 0170 User Action:...
  • Page 102 Information only; no action is required • FQXSPSD0007L: Array critical asserted on drive [arg1] in the enclosure/chassis (MTM-S/N: [arg2]). This message is for the use case when an implementation has detected that an Array is Critical. Severity: Error Serviceable: Yes Automatically notify Support: No Alert Category: Critical - Hard Disk drive SNMP Trap ID: 5...
  • Page 103 SNMP Trap ID: 22 CIM Prefix: PLAT CIM ID: 0163 User Action: Complete the following steps until the problem is solved: 1. If drive was intentionally removed, make sure that there is a filler in the drive bay. 2. Make sure that the drive is correctly seated. 3.
  • Page 104 Severity: Info Serviceable: No Automatically notify Support: No Alert Category: Critical - Hard Disk drive SNMP Trap ID: 5 CIM Prefix: PLAT CIM ID: 0175 User Action: Information only; no action is required • FQXSPSD2006I: Array in system [ComputerSystemElementName] has been restored. This message is for the use case when an implementation has detected that a Failed Array has been Restored.
  • Page 105 Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: PLAT CIM ID: 0163 User Action: Complete the following steps until the problem is solved: 1. If drive was intentionally removed, make sure that there is a filler in the drive bay. 2.
  • Page 106 1. Make sure that the certificate that you are importing is correct and properly generated. 2. If problem persists, collect Service Data log. 3. Contact Lenovo Support. • FQXSPSE4001I: Remote Login Successful. Login ID: [arg1] using [arg2] from [arg3] at IP address [arg4].
  • Page 107 SNMP Trap ID: 30 CIM Prefix: IMM CIM ID: 0014 User Action: Information only; no action is required. • FQXSPSE4002I: Security: Userid: [arg1] using [arg2] had [arg3] login failures from WEB client at IP address [arg4]. This message is for the use case where a user has failed to log in to a Management Controller from a web browser.
  • Page 108 1. Make sure that the certificate that you are importing is correct and properly generated / certificate CSR is correct 2. If problem persists, collect Service Data log. 3. Contact Lenovo Support. • FQXSPSE4007I: Security: Userid: [arg1] using [arg2] had [arg3] login failures from an SSH client at IP address [arg4].
  • Page 109 Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0075 User Action: Information only; no action is required. • FQXSPSE4009I: LDAP Server configuration set by user [arg1]: SelectionMethod=[arg2], DomainName=[arg3], Server1=[arg4], Server2=[arg5], Server3=[arg6], Server4=[arg7]. A user changed the LDAP server configuration Severity: Info Serviceable: No...
  • Page 110 Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0092 User Action: Information only; no action is required. • FQXSPSE4013I: Secure LDAP [arg1] by user [arg2]. A user enables or disables Secure LDAP services Severity: Info Serviceable: No Automatically notify Support: No...
  • Page 111 A user changes the Global Login Account Security Settings to Legacy Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0099 User Action: Information only; no action is required. • FQXSPSE4017I: User [arg1] created. A user account was created Severity: Info Serviceable: No...
  • Page 112 Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0103 User Action: Information only; no action is required. • FQXSPSE4021I: User [arg1] custom privileges set: [arg2][arg3][arg4][arg5][arg6][arg7][arg8][arg9]. User account priveleges assigned Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID:...
  • Page 113 Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0107 User Action: Information only; no action is required. • FQXSPSE4025I: SSH Client key removed from user [arg1] by user [arg2] from [arg3] at IP address [arg4].
  • Page 114 Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Remote Login SNMP Trap ID: 30 CIM Prefix: IMM CIM ID: 0153 User Action: Information only; no action is required. • FQXSPSE4029I: Security: Userid: [arg1] had [arg2] login failures from SNMP client at IP address [arg3].
  • Page 115 Serviceable: No Automatically notify Support: No Alert Category: System - Remote Login SNMP Trap ID: 30 CIM Prefix: IMM CIM ID: 0157 User Action: Information only; no action is required. • FQXSPSE4033I: Login ID: [arg1] from [arg2] at IP address [arg3] has been logged off. This message is for the use case where a user has been logged off of a Management Controller.
  • Page 116 SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0190 User Action: Information only; no action is required. • FQXSPSE4037I: Crypto mode modified from [arg1] to [arg2] by user [arg3]. Crypto mode modified Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0218...
  • Page 117 User Action: The user account you input has expired. • FQXSPSE4041I: Security: Userid: [arg1] had [arg2] login failures from a SFTP client at IP address [arg3]. This message is for the use case where a user has failed to log in to a Management Controller from SFTP. Severity: Info Serviceable: No Automatically notify Support: No...
  • Page 118 User Action: Information only; no action is required. • FQXSPSE4045I: The Salt of user [arg1] third-party password has been [arg2] by user [arg3] from [arg4] at IP address [arg5]. This message is for the use case where a user successfully manage the third-party password salt. Severity: Info Serviceable: No Automatically notify Support: No...
  • Page 119 User Action: Information only; no action is required. • FQXSPSE4049I: Role [arg1] is assigned to user [arg2] by user [arg3]. Role is assgned Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0248 User Action: Information only;...
  • Page 120 Using XCC web or LSA or Storcli to check the status of every virtual disk on your system, resolve the problem on the problematic virtual disk(s). • FQXSPSR2001I: Sensor [SensorElementName] has deasserted the transition to non-recoverable from a less severe state. This message is for the use case when an implementation has detected that the Sensor transition to non- recoverable from less severe has deasserted.
  • Page 121 Information only; no action is required. • FQXSPSS4003I: License key for [arg1] removed by user [arg2]. A user removes a License Key Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0097 User Action: Information only;...
  • Page 122 Tier Change Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: 22 CIM Prefix: IMM CIM ID: 0222 User Action: Information only; no action is required. • FQXSPSS4008I: The [arg1] setting has been changed to [arg2] by user [arg3]. The setting has been changed by user Severity: Info Serviceable: No...
  • Page 123 Severity: Info Serviceable: No Automatically notify Support: No Alert Category: none SNMP Trap ID: CIM Prefix: IMM CIM ID: 0033 User Action: Complete the following steps until the problem is solved: 1. Make sure that the certificate that you are importing is correct. 2.
  • Page 124 • FQXSPUN0009G: Sensor [SensorElementName] has asserted. This message is for the use case when an implementation has detected a Sensor has asserted. Severity: Warning Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: CIM Prefix: PLAT CIM ID: 0508 User Action: Reboot the system.
  • Page 125 SNMP Trap ID: 50 CIM Prefix: PLAT CIM ID: 0530 User Action: Complete the following steps: 1. Check the Lenovo support site for an applicable service bulletin or firmware update that applies to this error. Chapter 2 XClarity Controller events...
  • Page 126 2. Reboot the system. 3. If the error continues, collect Service Data logs. Contact Lenovo Support. • FQXSPUN0026I: Device [LogicalDeviceElementName] has been added. This message is for the use case when an implementation has detected a Device was inserted. Severity: Info...
  • Page 127 • FQXSPUN2012I: Sensor [SensorElementName] has deasserted. This message is for the use case when an implementation has detected a Sensor has deasserted. Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: CIM Prefix: PLAT CIM ID: 0509 User Action: Information only;...
  • Page 128 Information only; no action is required. • FQXSPUN2023I: Sensor [SensorElementName] has deasserted the transition to non-recoverable. This message is for the use case when an implementation has detected that the Sensor transition to non- recoverable has deasserted. Severity: Info Serviceable: No Automatically notify Support: No Alert Category: Critical - Other SNMP Trap ID: 50...
  • Page 129 3. If problem persists, collect Service Data log. 4. Contact Lenovo Support. • FQXSPUP4001I: Flash of [arg1] from [arg2] succeeded for user [arg3] . This message is for the use case where a user has successfully flashed the firmware component (MC Main Application, MC Boot ROM, BIOS, Diagnostics, System Power Backplane, Remote Expansion Enclosure Power Backplane, Integrated System Management).
  • Page 130 4. If problem persists, collect Service Data log. 5. Contact Lenovo Support. • FQXSPUP4004I: XCC firmware mismatch between nodes/servers [arg1] and [arg2]. Please attempt to flash the XCC firmware to the same level on all nodes/servers.
  • Page 131 3. If problem persists, collect Service Data log. 4. Contact Lenovo Support. • FQXSPWD0000I: Watchdog Timer expired for [WatchdogElementName]. This message is for the use case when an implementation has detected a Watchdog Timer Expired.
  • Page 132 • FQXSPWD0003I: Power cycle of system [ComputerSystemElementName] initiated by watchdog [WatchdogElementName]. This message is for the use case when an implementation has detected a Power Cycle by Watchdog occurred. Severity: Info Serviceable: No Automatically notify Support: No Alert Category: System - Other SNMP Trap ID: CIM Prefix: PLAT CIM ID: 0374 User Action:...
  • Page 133: Chapter 3. Uefi Events

    UEFI error messages can be generated when the server starts up (POST) or while the server is running. UEFI error messages are logged in the Lenovo XClarity Controller event log in the server. For each event code, the following fields are displayed: Event identifier An identifier that uniquely identifies an event.
  • Page 134 Table 3. Events organized by severity (continued) Message String Severity Event ID FQXSFMA0001I DIMM [arg1] Disable has been recovered. [arg2] Informational The uncorrectable memory error state has been cleared. Informational FQXSFMA0002I FQXSFMA0006I [arg1] DIMM [arg2] has been detected, the DIMM serial number is Informational [arg3].
  • Page 135 Table 3. Events organized by severity (continued) Message String Severity Event ID FQXSFPU4059I User requested to skip freezing lock of AHCI-attached SATA drives. Informational System UEFI accepted the request and will execute priot to OS boot. FQXSFPU4060I Skipped freezing lock of AHCI-attached SATA drives. Informational FQXSFPU4061I Restored default locking behavior of AHCI-attached SATA drives.
  • Page 136 Table 3. Events organized by severity (continued) Message String Severity Event ID FQXSFIO0025I An error has been detected by the IIO on processor [arg1]. The index Warning of the IIO stack is [arg2]. The type of IIO Internal Error is [arg3]. Please check error logs for additional downstream device error data.
  • Page 137 Table 3. Events organized by severity (continued) Message String Severity Event ID FQXSFMA0053G An uncorrected memory error has been recovered by mirror on DIMM Warning [arg1] at address [arg2].[arg3] FQXSFMA0054G Mirror failover operation was successful. DIMM [arg1] has failed over Warning to the mirrored DIMM [arg2].[arg3] FQXSFMA0054M...
  • Page 138 Table 3. Events organized by severity (continued) Message String Severity Event ID FQXSFDD0004M DRIVER HEALTH PROTOCOL: Reports 'System Shutdown' Required Error Controller. FQXSFIO0005M An intra-board UPI failure has been detected on the link between Error processor [arg1] port [arg2] and processor [arg3] port [arg4]. FQXSFIO0006M An inter-board UPI failure has been detected on the link between Error...
  • Page 139 Table 3. Events organized by severity (continued) Message String Severity Event ID FQXSFMA0010K Invalid memory configuration for Sparing Mode. Please correct Error memory configuration. [arg1] FQXSFMA0023M Error has occurred in NVDIMM flash. NVDIMM backup/restore may Error not operate correctly. [arg1] FQXSFMA0024M Error has occurred in NVDIMM Supercap.
  • Page 140: List Of Uefi Events

    2. Search for the driver menu from System Settings and change settings appropriately. 3. Save settings and restart the system. 4. If the problem persists, collect Service Data logs. 5. Contact Lenovo Support. • FQXSFDD0002M: DRIVER HEALTH PROTOCOL: Reports 'Failed' Status Controller. Severity: Warning...
  • Page 141 Complete the following steps: 1. Reboot the system. 2. Reflash the adapter firmware. 3. If the problem persists, collect Service Data logs. 4. Contact Lenovo Support. • FQXSFDD0003I: DRIVER HEALTH PROTOCOL: Reports 'Reboot' Required Controller. Severity: Warning User Action: Complete the following steps: 1.
  • Page 142 User Action: Complete the following steps: 1. Check Lenovo support site for an applicable service bulletin or UEFI firmware update that applies to this error. 2. A/C cycle the system. 3. If the problem persists, collect Service Data logs. 4. Contact Lenovo Support.
  • Page 143 Severity: Error User Action: Complete the following steps: 1. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this error. 2. If the problem persists, collect Service Data logs. 3. Contact Lenovo Support. • FQXSFIO0007M: An error has been detected by the IIO on Bus [arg1]. The value of Global Fatal Error Status register is [arg2].
  • Page 144 1. Check Lenovo support site for an applicable device driver, firmware update, version of service information for this product or other information that applies to this error. Load new device driver and any required firmware updates. 2. If this device and/or any attached cables were recently installed, moved, serviced or upgraded.
  • Page 145 1. If this PCIe device and/or any attached cables were recently installed, moved, serviced or upgraded, reseat adapter and any attached cables. 2. Check Lenovo support site for any applicable service bulletin or UEFI or adapter firmware update that applies to this error.(NOTE: It may be necessary to disable unused option ROMs from UEFI F1 setup, OneCLI utility, or using adapter manufacturer utilities so that adapter firmware can be updated.)
  • Page 146 1. Check the log for a separate error related to an associated PCIe device and resolve that error. 2. Check the Lenovo support site for an applicable service bulletin or firmware update for the system or adapter that applies to this error.
  • Page 147 1. Check the log for a separate error related to an associated PCIe device or NVME disk and resolve that error. 2. Check the Lenovo support site for an applicable service bulletin or firmware update for the system or adapter that applies to this error.
  • Page 148 Severity: Warning User Action: Complete the following steps: 1. Check Lenovo support site for an applicable service bulletin or firmware update for the system or adapter that applies to this error. 2. If the problem persists, collect Service Data logs.
  • Page 149 1. Check the log for a separate error related to an associated PCIe device or NVME disk and resolve that error. 2. Check the Lenovo support site for an applicable service bulletin or firmware update for the system or adapter that applies to this error.
  • Page 150 1. Reseat the affected DIMM (Note: The event Log might contain a recent FQXSFMA0011I event denoting detected change in DIMM population that could be related to this problem.) 2. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this memory error.
  • Page 151 6. Reflash UEFI firmware. 7. If the problem persists, collect Service Data logs. 8. Contact Lenovo Support. • FQXSFMA0006I: [arg1] DIMM [arg2] has been detected, the DIMM serial number is [arg3]. Severity: Info User Action: Complete the following steps: 1. If this information event is logged in the XCC event log, the server does not have qualified memory installed.
  • Page 152 5. Contact Lenovo Support. • FQXSFMA0009I: Invalid memory configuration for Mirror Mode has been recovered. [arg1] Severity: Info User Action: Information only; no action is required. • FQXSFMA0009K: Invalid memory configuration for Mirror Mode. Please correct memory configuration. [arg1] Severity: Error...
  • Page 153 DIMM connector on that memory channel. 2. If no problem is observed on the BBU connectors or the problem persists, Check the Lenovo support site for an applicable service bulletin or firmware update that applies to this memory error.
  • Page 154 BBU connector on that memory channel. 2. If no problem is observed on the BBU connectors or the problem persists, Check the Lenovo support site for an applicable service bulletin or firmware update that applies to this memory error.
  • Page 155 2. Boot to F1 setup and enable the DIMM. Reboot the system. 3. Update UEFI firmware to the latest version. 4. If the problem persists, collect Service Data logs. 5. Contact Lenovo Support. • FQXSFMA0028K: Memory Capacity exceeds CPU limit. [arg1] Severity: Error...
  • Page 156 2. Back up data. 3. Check if the PMEM meets warranty terms. a. If the PMEM meets the warranty terms, contact Lenovo Support for PMEM replacement. b. If the PMEM does not meet the warranty terms, order a new comparable PMEM through an authorized Lenovo reseller.
  • Page 157 3. This error message will provide the UID of the missing PMEM, 4. Use Lenovo Service Client or contact Lenovo Support to parse log to get correct location for PMEM Find the missing PMEM and install it in the correct location.
  • Page 158 5. If an error occurs, follow steps 1 and 4 to get details on new error message. 6. If the problem persists, collect Service Data logs. 7. Contact Lenovo Support. • FQXSFMA0037G: Intel Optane PMEM interleave set (DIMM [arg1]) is migrated from another system (Platform ID: [arg2]), these migrated PMEMs are not supported nor warranted in this system.
  • Page 159 4. If the issue is not resolved then contact Lenovo Support. • FQXSFMA0040K: Invalid Intel Optane PMEM configuration detected. Please verify PMEM configuration is valid. Severity: Warning User Action: Complete the following steps: 1. Check system spec and follow the rules for populating PMEM in correct order.
  • Page 160 DIMM population that could be related to this problem) 3. Restore A/C power and power on the system. 4. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this memory error.
  • Page 161 3. Reseat the failing DIMM identified by LightPath and/or event log entry 4. Restore A/C power and power on the system. 5. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this memory error.
  • Page 162 Severity: Error User Action: Complete the following steps: 1. Check Lenovo support site for a firmware update required for this processor and install that update, if applicable. 2. If the problem persists, collect Service Data logs. 3. Contact Lenovo Support.
  • Page 163 2. Check Lenovo support site for a firmware update required for this Processor and install that update, if applicable. 3. If the problem persists, collect Service Data logs. 4. Contact Lenovo Support. • FQXSFPU0003K: A processor mismatch has been detected between one or more processors in the system.
  • Page 164 1. Verify that matching processors are installed in the correct processor sockets. Correct any mismatch issues found. 2. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this processor error. 3. If the problem persists, collect Service Data logs.
  • Page 165 1. Verify that matching processors are installed in the correct processor sockets. Correct any mismatch found. 2. Check the Lenovo support site for an applicable service bulletin or firmware update that applies to this processor error. 3. If the problem persists, collect Service Data logs.
  • Page 166 1. Verify that matching processors are installed in the correct processor sockets. Correct any mismatch found. 2. Check the Lenovo support site for an applicable service bulletin or firmware update that applies to this processor error. 3. If the problem persists, collect Service Data logs.
  • Page 167 Severity: Error User Action: Complete the following steps: 1. Check Lenovo support site for an applicable service bulletin or UEFI firmware update that applies to this error. 2. Reboot the system. 3. If the problem persists, collect Service Data logs.
  • Page 168 Severity: Error User Action: Complete the following steps: 1. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this error. 2. Reflash UEFI image. 3. Undo recent system changes (settings or devices added). Verify that the system boots. Then, re- install options one at a time to locate the problem.
  • Page 169 3. Undo recent system changes (settings or devices added). Verify that the system boots. Then, re- install options one at a time to locate the problem. 4. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this error. Update UEFI firmware if applicable.
  • Page 170 1. Perform a virtual reseat or AC cycle the server. 2. If the problem returns Collect Service Data log. 3. Contact Lenovo Support. • FQXSFPU4033F: TPM Firmware recovery is in progress. Please DO NOT power off or reset system. Severity: Warning User Action: Information only;...
  • Page 171 Information only; no action is required. • FQXSFPU4051G: Undefined TPM_POLICY found Severity: Warning User Action: Complete the following steps: 1. Reboot the system. 2. If the problem persists, collect Service Data logs. 3. Contact Lenovo Support. Chapter 3 UEFI events...
  • Page 172 User Action: Complete the following steps: 1. Reboot the system. 2. If the problem persists, collect Service Data logs. 3. Contact Lenovo Support. • FQXSFPU4053G: System TPM_POLICY does not match the planar. Severity: Warning User Action: Complete the following steps: 1.
  • Page 173 User Action: Information only; no action is required. • FQXSFPU4059I: User requested to skip freezing lock of AHCI-attached SATA drives. System UEFI accepted the request and will execute priot to OS boot. Severity: Info User Action: Complete the following steps: 1.
  • Page 174 1. If the CMOS clear was user initiated this event can be safely ignored and no further action is required. 2. If the system was recently installed, moved, or serviced, make sure the battery is properly seated. 3. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this error.
  • Page 175 4. Reflash XCC Firmware. 5. If the problem persists, collect Service Data logs. 6. Contact Lenovo Support. • FQXSFSM0007I: The XCC System Event log (SEL) is full. Severity: Info User Action: Complete the following steps: 1. Use BMC Web Interface to clear event logs.
  • Page 176 3. Connect AC power to the system. 4. Power on system and retry. 5. If the problem persists, collect Service Data logs. 6. Contact Lenovo Support. • FQXSFTR0001L: An invalid date and time have been detected. Severity: Warning User Action: Complete the following steps: 1.
  • Page 177: Chapter 4. Xclarity Provisioning Manager Events

    Chapter 4. XClarity Provisioning Manager events The following events can be generated by the Lenovo XClarity Provisioning Manager. For each event code, the following fields are displayed: Event identifier An identifier that uniquely identifies an event. Event description The logged message string that appears for an event.
  • Page 178 Table 4. Events organized by severity (continued) Message String Severity Event ID FQXPMEM0004I Launching diagnostic program Informational FQXPMEM0005I boot diagnostic program success Informational FQXPMER0002I Clearing RAID configuration and internal storage Informational FQXPMER0003I RAID configuration cleared successfully Informational FQXPMER0004I Internal storage drives erased successfully Informational FQXPMER0005I All system logs cleared successfully...
  • Page 179 Table 4. Events organized by severity (continued) Message String Severity Event ID FQXPMOS0002K Failed to read Deployment Manager Signature from USB. Warning FQXPMOS0003K Failed to copy Windows boot files to target Warning FQXPMOS0004K BMC Communication Failed: EMMC2USB Mount Failure. Warning Warning FQXPMOS0005K BMC communication failed: DRIVER Mount Failure.
  • Page 180: List Of Xclarity Provisioning Manager Events

    Failed to execute reboot BMC command Error List of XClarity Provisioning Manager events This section lists all messages that can be sent from the Lenovo XClarity Provisioning Manager. • FQXPMCL0001K: Bootx64.efi is not found. Failed to Boot OS. Severity: Warning User Action: 1.
  • Page 181 3. Reboot system and retry OS booting. 4. Perform AC reset or virtual reseat. Note: When performing AC reset, after powering off AC, wait several seconds before powering on AC. After AC power is restored, power on the host system. 5.
  • Page 182 • FQXPMCL0006K: Failed to export raid config. Severity: Warning User Action: 1. Check the following Lenovo support site for information on supported RAID adapters. http://www. lenovo.com/us/en/serverproven/index.shtml 2. Ensure RAID adapter, LXPM, and UEFI firmware are at the latest levels. 3. Ensure the state of the RAID adapter and disk drives are normal.
  • Page 183 6. Reboot the machine and retry the import of the RAID configuration. 7. If the problem persists, contact technical support. • FQXPMCL0008I: Export uefi settings successfully. Severity: Info User Action: Information only; no action is required. • FQXPMCL0008K: Failed to export uefi settings. Severity: Warning User Action: 1.
  • Page 184 3. Retry the export of BMC setting. 4. If the problem persists, contact technical support. • FQXPMCL0011I: Import bmc settings successfully. Severity: Info User Action: Information only; no action is required. • FQXPMCL0011K: Failed import bmc settings. Severity: Warning User Action: 1.
  • Page 185 Information only; no action is required. • FQXPMEM0005I: boot diagnostic program success Severity: Info User Action: Information only; no action is required. • FQXPMEM0006M: Unable to locate diagnostic firmware image Severity: Error User Action: 1. Restart BMC via supported method and reboot the system. 2.
  • Page 186 Severity: Error User Action: 1. Restart the system and retry the operation again. 2. If the problem persists, contact technical support. • FQXPMER0003I: RAID configuration cleared successfully Severity: Info User Action: Information only; no action is required. • FQXPMER0003M: Failed to erase internal storage drives Severity: Error User Action: 1.
  • Page 187 3. If the problem persists, contact technical support. • FQXPMER0006I: UEFI factory default settings loaded successfully Severity: Info User Action: Information only; no action is required. • FQXPMER0006M: Failed to load XCC factory default settings Severity: Error User Action: 1. Restart BMC via supported method and reboot the system. 2.
  • Page 188 Note: When performing AC reset, after powering off AC, wait several seconds before powering on AC. After AC power is restored, power on the host system. 5. If the problem persists, contact technical support. • FQXPMOS0002K: Failed to read Deployment Manager Signature from USB. Severity: Warning User Action: 1.
  • Page 189 User Action: 1. Ensure proper operation of the virtual USB connection. 2. Restart BMC via supported method and reboot the system. 3. Reflash BMC firmware. 4. Retry OS deployment. 5. Perform AC reset or virtual reseat. Note: When performing AC reset, after powering off AC, wait several seconds before powering on AC.
  • Page 190 • FQXPMOS0009K: Current System Boot Mode is Legacy. LXPM OS installation only support UEFI Mode. Severity: Warning User Action: 1. Change boot mode to UEFI mode 2. Retry OS deployment. • FQXPMOS0028I: [arg1] OS installed Severity: Info User Action: Information only; no action is required. •...
  • Page 191 User Action: 1. Remove A/C from the server and reseat all drives, backplanes, RAID adapters, expanders (if any), and cables. 2. Ensure device firmware is at the latest level. 3. Retry the test. 4. If the problem persists, contact technical support. •...
  • Page 192 Severity: Error User Action: 1. Do one of the following: – If the affected drive(s) are detected by the system, update the disk drive firmware and reboot the server. – If the affected drive(s) are not detected by the system or failing to respond: a.
  • Page 193 User Action: 1. Check the following Lenovo support site for information on supported RAID adapters. http://www. lenovo.com/us/en/serverproven/index.shtml 2. Ensure RAID adapter, LXPM, and UEFI firmware are at the latest levels. 3. If the problem persists, contact technical support. • FQXPMSR0011K: Failed to change disk drives' state.
  • Page 194 3. Verify proper physical connection of the disk drive, SAS expander (if applicable)and RAID adapter. 4. Reboot the machine and retry to remove the existing virtual disk. 5. If the problem persists, contact technical support. • FQXPMSR0032I: Removed existing virtual disk successfully. Severity: Info User Action: Information only;...
  • Page 195 Severity: Warning User Action: 1. Restart BMC via supported method and reboot the system. 2. Reflash BMC firmware. 3. Perform AC reset or virtual reseat. Note: When performing AC reset, after powering off AC, wait several seconds before powering on AC.
  • Page 196 Note: When performing AC reset, after powering off AC, wait several seconds before powering on AC. After AC power is restored, power on the host system. 4. If the problem persists, try a different Lenovo tool to perform the update (eg. XClarity Administrator, XClarity Controller, or XClarity Essential OneCLI).
  • Page 197 Note: When performing AC reset, after powering off AC, wait several seconds before powering on AC. After AC power is restored, power on the host system. 6. If the problem persists, try a different Lenovo tool to perform the update (eg. XClarity Administrator, XClarity Controller, or XClarity Essential OneCLI).
  • Page 198 Note: When performing AC reset, after powering off AC, wait several seconds before powering on AC. After AC power is restored, power on the host system. 4. If the problem persists, try a different Lenovo tool to perform the update (eg. XClarity Administrator, XClarity Controller, or XClarity Essential OneCLI).
  • Page 199 Note: When performing AC reset, after powering off AC, wait several seconds before powering on AC. After AC power is restored, power on the host system. 4. If the problem persists, contact technical support. • FQXPMVD0001H: Failed to get VPD data. Severity: Warning User Action: 1.
  • Page 200 ThinkSystem SD650 V3 / ThinkSystem SD650-I V3 Neptune DWC Trays and DW612S Neptune DWC Enclosure Messages and Codes Reference...
  • Page 201: Appendix A. Getting Help And Technical Assistance

    Appendix A. Getting help and technical assistance If you need help, service, or technical assistance or just want more information about Lenovo products, you will find a wide variety of sources available from Lenovo to assist you. On the World Wide Web, up-to-date information about Lenovo systems, optional devices, services, and support are available at: http://datacentersupport.lenovo.com...
  • Page 202: Collecting Service Data

    Collecting service data To clearly identify the root cause of a server issue or at the request of Lenovo Support, you might need collect service data that can be used for further analysis. Service data includes information such as event logs and hardware inventory.
  • Page 203: Contacting Support

    Support when certain serviceable events occur in Lenovo XClarity Administrator and the managed endpoints. You can choose to send diagnostic files to Lenovo Support using Call Home or to another service provider using SFTP. You can also manually collect diagnostic files, open a problem record, and send diagnostic files to the Lenovo Support.
  • Page 204 ThinkSystem SD650 V3 / ThinkSystem SD650-I V3 Neptune DWC Trays and DW612S Neptune DWC Enclosure Messages and Codes Reference...

Table of Contents