Dc Injection Brake (Pr. 10 To Pr. 12) - Mitsubishi Electric FR-E560 Series Instruction Manual

Transistorized inverter
Table of Contents

Advertisement

4.2.7

DC injection brake (Pr. 10 to Pr. 12)

Pr. 10 "DC injection brake operation frequency"
Pr. 11 "DC injection brake operation time"
Pr. 12 "DC injection brake voltage"
By setting the DC injection brake voltage (torque), operation time and operation starting
frequency, the stopping accuracy of positioning operation, etc. or the timing of operating
the DC injection brake to stop the motor can be adjusted according to the load.
Parameter
Factory
Number
Setting
10
11
12
<Setting>
• Use Pr. 10 to set the frequency at which the DC injection brake operation is started.
• Use Pr. 11 to set the period during when the brake is operated.
• Use Pr. 12 to set the percentage of the power supply voltage.
Install a mechanical brake. No holding torque is provided.
Setting
Range
3Hz
0 to 120Hz
0.5s
0 to 10 s
2%
0 to 30%
CAUTION
Pr.12
DC injection
Operation
brake voltage
voltage
80
PARAMETERS
Operation
Pr.10
frequency
Time
Time
Operation time
Pr.11