Mitsubishi Electric FR-E560 Series Instruction Manual page 29

Transistorized inverter
Table of Contents

Advertisement

Type
Symbol
A, B, C
Alarm output
Inverter
RUN
running
Frequency
FU
detection
Open collector
SE
output common
Analog signal
AM
output

PU connector
*1: Low indicates that the open collector output transistor is on (conducts). High
indicates that the transistor is off (does not conduct).
*2: Not output during inverter resetting.
Terminal
Name
Change-over contact output indicating that
the output has been stopped by the inverter
protective function activated. 230VAC 0.3A,
30VDC 0.3A. Alarm: discontinuity across B-
C (continuity across A-C), normal:
continuity across B-C (discontinuity across
A-C).
Switched low when the inverter output
frequency is equal to or higher than the
starting frequency (factory set to 0.5Hz,
variable). Switched high during stop or DC
injection brake operation (*1).
Permissible load 24VDC 0.1A.
Switched low when the output frequency
has reached or exceeded the detection
frequency set as appropriate. Switched
high when the output frequency is below
the detection frequency (*1).
Permissible load 24VDC 0.1A
Common to the RUN and FU terminals
One selected from output
frequency, motor current
and output voltage is output
(*2). The output signal is
proportional to the
magnitude of each
monitoring item.
With the operation panel connector, communication can
be made using the RS-485 protocol.
• Conforming Standard
• Transmission format
• Communication speed : Maximum 19200bps
• Overall length
INSTALLATION AND WIRING
Description
Factory setting of output
item:
Frequency output signal 0
to 10 VDC
Permissible load current
1mA
: EIA Standard RS-485
: Multi-drop link system
: 500m (1640.40 feet)
19
Output
terminal
function
selection
(Pr. 190 to
Pr. 192)
changes
terminal
functions.