8) Install the inverter securely in the vertical direction with screws or bolts.
3) Note on ambient
temperatures
Measurement
position
5cm
FR-E500
(1.97 inch)
5cm
Measurement
(1.97 inch)
position
7) For installation in an enclosure
Ventilation
fan
Inverter
(Correct example) (Incorrect example)
Position of Ventilation Fan
8) Vertical mounting
4) Clearances around the inverter
1cm (0.39inch)
or more*
5cm
(1.97 inch)
*5cm (1.97inch) or more for 5.5K and 7.5K
These clearances are also necessary for changing the cooling fan.
(The 1.5K or more is provided with a cooling fan)
Inverter
INSTALLATION AND WIRING
10cm (3.94inch)
or more
1cm (0.39inch)
FR-E500
or more*
10cm (3.94inch)
or more
Inverter
Inverter
Built-in cooling fan
(Correct example)
When more than one inverter is contained
15
Leave sufficient
Cooling air
clearances above
and under the
inverter to ensure
adequate ventilation.
Cooling fan
built in the
inverter
Inverter
Inverter
(Incorrect example)