Restoring Data From An Unencrypted Backup Data - Siemens SINAMICS S200 Operating Instructions Manual

Pulse train servo drive system
Hide thumbs Also See for SINAMICS S200:
Table of Contents

Advertisement

Commissioning (web server)
7.4 Functions and menus
Description
The converter backs up the following data and settings:
• Communication interface settings
• Parameters (including safety parameters)
• Security settings
• UMAC data
• Web server settings:
– Modified settings in window "Drive status" on the home page
– User-defined parameter lists
– Support settings
– Save changes manually/automatically
• Displayed parameters (display standard parameters/all parameters):
– Standard parameters
– View all parameters
– Display brightness
The converter firmware files are not backed up.
7.4.6.4

Restoring data from an unencrypted backup data

Requirement
• You have an unencrypted backup file of the converter on your operating unit.
• Rights required for active user management (UMAC):
– "Create backup or load drive data to Startdrive"
Procedure
1. Call the "Backup and restore" menu.
2. Navigate to the "Restore drive data from backup file" area.
3. Use the "Click to select file, or drag and drop file here" button to select the backup file.
4. To restore the drive data, proceed as described below depending on the specific application.
This step is included in the following diagrams as step 3.
204
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA