Communication Interface; Making The Operating Instructions Available For The Web Server Information System - Siemens SINAMICS S200 Operating Instructions Manual

Pulse train servo drive system
Hide thumbs Also See for SINAMICS S200:
Table of Contents

Advertisement

7.2.4

Communication interface

Description
The following interface is available for accessing the converter:
Interface
Service interface X127
7.2.5
Making the operating instructions available for the web server information
system
Overview
For selected topics, you can use the information system of the web server to access the product
documentation directly. To do this, you must make the product documentation available on a
prepared SD card.
Requirement
• You have an empty SD card with a maximum storage capacity of 32 GB (e.g.
6SL5570-0GC00-0AA0) onto which you can load the product documentation.
• You have connected a suitable SD card reader to your PC.
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA
Information
The default access to the web server is via the service interface X127.
Service interface X127 is intended for commissioning and diagnostics, which
means that it must always be accessible.
Defaults:
IP address: 169.254.11.22
Subnet mask: 255.255.0.0
Data transfer via HTTPS is activated in the factory setting.
Restrictions:
Only local access is allowed.
Only local networking in a closed and locked electrical cabinet is permis‐
sible.
For remote access to the electrical cabinet, you must apply additional In‐
dustrial Cybersecurity measures to prevent misuse through sabotage, data
manipulation by unqualified persons and interception of confidential data.