Using Several Single-Phase Converters In Machines And Plants - Siemens SINAMICS S200 Operating Instructions Manual

Pulse train servo drive system
Hide thumbs Also See for SINAMICS S200:
Table of Contents

Advertisement

Procedure
1. Assemble the X1 plug to the converter.
2. Attach the cable terminals to the plug as shown below:
Figure 6-3
Figure 6-4
More information
For more information about cable requirements, see Section "Cables and connectors
(Page 124)".
For more information about assembling cable terminals, see Section "Assembling cables
(Page 734)".
6.4.3

Using several single-phase converters in machines and plants

Overview
Evaluate the input currents of single-phase converters in your machine or plant in terms of
harmonics and unbalance.
Description
In unfavorable cases, the harmonic currents of several converters in the neutral conductor (N)
add up to a value greater than the currents of the line conductors (L1, L2, L3). The current-
carrying capacity of the neutral conductor must be sufficient for this.
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA
Connecting to the single-phase mains supply network
Connecting to the three-phase mains supply network
Connecting
6.4 Connecting the mains supply
127

Advertisement

Table of Contents
loading

Table of Contents