SMC Networks ZSE20(F) ISE20 Manual page 23

Digital pressure switch
Table of Contents

Advertisement

The Pressure switch turns on within a set pressure range (from P1L to P1H) during window comparator
mode. Set P1L, the lower limit of the switch operation, and P1H, the upper limit of the switch operation and
WH1 (hysteresis) following the instructions given on page 21.
(When reversed output is selected, the sub display (left) shows [n1L] and [n1H].)
Please refer to the "List of output modes" on page
30
for the relationship between the set values and
operation.
: Setting of the normal/reverse output switching and hysteresis/window comparator mode switching are
performed with the function selection mode [F 1] Setting of OUT1.
-22-
No.PS※※-OMS0007-D