Appendix B: 4/2 Reporting Codes; Table 10: 4/2 Reporting Codes - Bosch FPT-DACT Operations & Installation Manual

Fire communicator
Table of Contents

Advertisement

FPT-DACT | Operation & Installation Guide |

Appendix B: 4/2 Reporting Codes

Table 10 lists the 4/2 codes supported by the FPT-DACT Fire Communicator. See RPT CODES for programming
information.

Table 10: 4/2 Reporting Codes

4/2 Report Code
Keypad
Number Key
SYSTEM IN TST*
[1]
SYS IN RPT*
[2]
SILENCE*
[3]
FIRE DRILL*
[4]
FIRE DRL RST*
[5]
OPEN RST RPT
[6]
LOW BATTERY
[7]
LOW BATT RST
[8]
AC FAILURE
[9]
AC FAIL RST
[1]
AUTO TST RPT
[2]
OFF NORM TST
[3]
PHONE 1 TRBL
[4]
PN 1 TRB RST
[5]
PHONE 2 TRBL
[6]
PN 2 TRB RST
[7]
SYSTEM TROUB*
[8]
SYS TRB RST*
[9]
MAN TST RPT
[1]
DATA LOST RP
[2]
EEPROM FAIL
[3]
RESET REBOOT*
[4]
SMK PWR TBL
[5]
SMK PWR RSTR
[6]
GND FLT TRBL
[7]
GND FLT RSTR
[8]
* Item is sent only when the FPT-DACT is configured to communicate with a D8024 or D10024/D10024A Analog FACP.
** Item is for future use.
1/05 | F01U002505B
Appendix B
Group
Definition
Number
1
System in Test. Sent for Walk Test operations.
1
System in Test Restore. Sent for Walk Test operations.
1
Silence. Sent when the [SILENCE] key is pressed.
1
Fire Drill. Sent for fire drill operations.
1
Fire Drill Restore. Sent for fire drill operations.
1
Open Reset Report. Sent when the [RESET] key is pressed.
1
Low Battery: Sent when a low battery input is active.
1
Low Battery Restore. Restoral occurs when a low battery input is active.
1
AC Failure. Sent when an AC Fail input is active.
2
AC Failure Restore. Restoral occurs for AC Failure.
2
Automatic Test Report. Sent for automatic communicator tests.
2
Off Normal at Test. Sent if the control panel is off-normal at the Automatic
Test time.
2
Phone Line 1 Trouble. Sent for Phone Line 1 problems.
2
Phone Line 1 Trouble Restore. Sent for Phone Line 1 problems.
2
Phone Line 2 Trouble. Sent for Phone Line 2 problems.
2
Phone Line 2 Trouble Restore. Sent for Phone Line 2 problems.
2
System Trouble. Sent for general system problems.
2
System Trouble Restore. Sent for general system problems.
3
Manual Test Report. Sent for manual communicator tests.
3
Data Lost Report. Sent if events occur too rapidly.
3
EEPROM Failure. Sent for EEPROM problems.
3
System power up and reboot.
3
Smoke Power Trouble. Sent for smoke detector power supply problems.
3
Smoke Power Trouble Restore. Sent for smoke detector power supply
problems.
3
Ground Fault Trouble. Sent for ground fault trouble problems.
3
Ground Fault Trouble Restore. Sent for ground fault trouble problems.
EN | 47