Programming The Fpt-Dact; Prog Time - Bosch FPT-DACT Operations & Installation Manual

Fire communicator
Table of Contents

Advertisement

FPT-DACT | Operation & Installation Guide |
5.4

Programming the FPT-DACT

The FPT-DACT uses scrolling menus to show the menu
choices. The Main Menu shows:
SYSTEM NORMAL
0: PROGRAM
1: STATUS
2: HISTORY
3: TEST
4: RESET
To enter the Programming Menu, press [0]. The
Programming Menu shows:

1: PROG TIME

2: PROG TIMERS
3: PROG INPUTS
4: PROG RELAY
5: PROG ACC'NTS
6: PROG FORMATS
7: PROG DEFLTS
8: SLAVE CONECTN
Once you enter the Programming Menu
(Level 2), you no longer need to press [0] to
re-enter the Programming Menu. If you press
[0] while already in the Programming Menu,
the keypad emits a three-beep error tone.
5.4. 1
PROG TIME
The PROG TIME feature provides programming
options for setting the system date and time,
establishing automatic testing times, and adhering to
daylight savings time.
To access the PROG TIME programming options:
At the Programming Menu, press [1] to select
1: PROG TIME. The window shows:
DATE/TIME
1: SYSTEM
2: AUTO TEST
3: DAYLIGHT SAV
Refer to the following sections for the PROG TIME
programming options.
1: SYSTEM
To access SYSTEM, select [0]: PROGRAM--->
[1]: PROG TIME--->[1]: SYSTEM. This option allows
you to set the current date and time for system
operations.
1/05 | F01U002505B
5.0 Programming
To set the current date and time for system operations:
1. At the Prog Time Submenu, press [1] to select
1: SYSTEM. The window shows:
ENTER DATE
MMDDYY: _________
2. Enter the date and press [# Command] to accept the
entry.
3. Press [* Clear] to move to the next feature.
4. Enter the time in 24-h format and press
[# Command] to accept the entry.
5. Press [* Clear] to return to the Prog Time (Date/
Time) scrolling menu. The keypad shows the entries
that were made before returning to the Prog Time
Menu.
2: AUTO TEST
To access AUTO TEST, select [0]: PROGRAM--->
[1]: PROG TIME--->[2]: AUTO TEST. This option
allows you to set the time the Auto Test is sent and how
often the Auto Test occurs.
To set the time the Automatic Test is sent and how often
an Auto Test occurs:
• At the Prog Time Submenu, press [2] to select
2: AUTO TEST. The window shows:
Refer to the following sections for the Automatic Test
programming options.
2: TEST FREQUENCY
To access TEST FREQUENCY, select
[0]: PROGRAM--->[1]: PROG TIME--->[2]: AUTO
TEST--->[2]: TEST FREQUENCY. Choosing this
option allows you to program how often the Auto Test
Reports are sent. The first test is sent when the system
time matches the next programmed test time. Subsequent
reports are sent to the selected intervals.
To program the frequency of Auto Test Reports:
1. At the Auto Test Submenu, press [2] to select
2: TEST FREQUENCY. The window shows:
ENTER TIME
HHMM: ___________
AUTOMATIC TEST
1: TEST TIME
2: TEST FREQUENCY