FPT-DACT | Operation & Installation Guide | 5.0 Programming
The 6:DISABLED option is not currently
supported.
2. Press the number key that corresponds to your
selection and then press [# Command]. The revised
setting appears in parentheses on the first line.
3. After programming this feature, press [* Clear] to
return to the Auto Test Submenu.
1: TEST TIME
To access TEST TIME, select
[0]: PROGRAM--->[1]: PROG TIME--->[2]: AUTO
TEST--->[1]: TEST TIME. This option allows you to
program the time of day the Auto Tests occur and uses a
24-h clock. For example, enter 2300 for 11:00 p.m.
To program the time an Auto Test occurs:
1. At the Auto Test Submenu, press [1] to select
1: TEST TIME. The window shows:
AUTO TEST TIME
HHMM: ___________
2. Enter the time in 24-h format and press
[# Command].
3. Press [* Clear] to return to the Auto Test Submenu.
If the test frequency is not programmed
before the test time, the first Auto Test is
not performed.
3: DAYLIGHT SAV
To access DAYLIGHT SAV, select [0]: PROGRAM
--->[1]: PROG TIME--->[3]: DAYLIGHT SAV. This
option enables the automatic adjustment of system time
for daylight savings. The adjustment dates are
pre-programed into the system.
To set the system for Daylight Savings Time:
1. At the Prog Time Submenu, press [3] to select
3: DAYLIGHT SAV. The window shows:
DAYLIGHT SAVING?
NO: YES (1)/NO (0)
2. The current setting precedes the colon (:) in the
second line. Press [1] to set DAYLIGHT SAV to
Yes. Press [0] to set it to No.
3. Press [# Command] to verify your selection.
4. After programming this feature, press [* Clear] to
return to the Prog Time Submenu.
1/05 | F01U002505B
5.4.2

PROG TIMERS

The PROG TIMERS feature allows you to set
time-related parameters for the AC Fail Delay and the
Display Rate.
To set time-related parameters for AC Fail Delay and
Display Rate:
At the Programming Menu, press [2] to select
1: PROG TIME. The window shows:
PROG TIMERS
1: AC FAIL DLY
2: DISPLAY RATE
See the following sections for the programming options.
1: AC FAIL DLY
To access AC FAIL DLY, select [0]: PROGRAM
--->[2]: PROG TIMERS--->[1]: AC FAIL DLY. The
window shows:
AC FAIL DLY(__)
1: WAIT FOR DC
2: WAIT DLY TIME
This option sets the number of hours the FPT-DACT
waits after an AC failure is signaled before sending an
AC Failure Report.
1: WAIT FOR DC
To access WAIT FOR DC, select [0]: PROGRAM
--->[2]: PROG TIMERS--->[1]: AC FAIL DLY--->
[1]: WAIT FOR DC.
Two input points must be programmed with one set for
AC Fail and the other for Low Battery. Once an AC Fail
signal is received on the AC Fail input, the FPT-DACT
waits for a low battery signal. The WAIT FOR DC
function causes the FPT-DACT to wait and then send
the AC Fail and Low Batt Reports simultaneously. The
current setting appears in parentheses on the first line.
When a Low Battery input, followed by an
AC Fail input activates, the AC Fail Report
is sent immediately.
To set the FPT-DACT to wait and send AC Fail and
Low Batt Reports simultaneously:
1. Press [1] and then [# Command]. The setting in
parentheses reflects the setting.
2. After programming this feature, press [* Clear] to
return to the Prog Timers Submenu.
EN | 34