4.2 Battery specification
Battery type
Battery quantity
Battery Voltage
Table 4 -2: Battery specification
4.3 Environmental specifications
Recommend storage temperature range
Ambient operating temperature range
Recommended ambient operating
temperature range
Relative humidity range
Table 4 -3: Environmental specifications
P-164000427
Revision 2
VRLA, 12 VDC
93PM 30-50 kW units:
1) 36 blocks, 216 cells per battery string, 2V per cell.
93PM 80-200 kW units:
1) 36 blocks, 216 cells per battery string, or
2) 40 blocks, 240 cells per battery string, 2V per cell.
93E 80-200 kVA units:
1) 36 blocks, 216 cells per battery string, or
2) 38 blocks, 228 cells per battery string, or
3) 40 blocks, 240 cells per battery string, 2V per cell.
Note! Battery strings with different battery quantity and
voltage must not be connected in parallel!
432 V (36 blocks) or 456V (38 blocks) or 480 V (40
blocks)
From -25 °C to +25 °C in the protective
package
From +5 °C to +40 °C
From +20 °C to +25 °C
5 to 95 % no condensation allowed
SMALL and LARGE BATTERY CABINET
User's and Installation Guide
18