Toshiba MMD-UP0721HFP-UL Service Manual page 68

Air-conditioner multi type
Hide thumbs Also See for MMD-UP0721HFP-UL:
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
No. of indoor
units from
which signal is
received
normally
E04/E06
E06
E07
Duplicated
indoor address
E08
E08
E09
E10
01:
Indoor-outdoor
communication
02:
Outdoor-outdoor
E12
E12
communication
E15
E15
Location
Description
System status
of
detection
Indoor unit
Indoor-outdoor
All stop
communication
circuit trouble
(E04)
I/F
Dropping out of
indoor unit
(E06)
I/F
Indoor-outdoor
All stop
communication
circuit trouble
(detected at
outdoor end)
Indoor unit
Duplicated
All stop
I/F
indoor address
Remote
Duplicated
Stop of
controller
master remote
corresponding
controller
unit
Indoor unit
Indoor inter-
Stop of
MCU
corresponding
communication
unit
trouble
I/F
Automatic
All stop
address starting
trouble
I/F
Indoor unit not
All stop
found during
automatic
address setting
- 68 -
Check code detection
Check items (locations)
condition(s)
Condition 1
• Check power supply to
One indoor unit or more
indoor unit.
(Is power turned on?)
initially communicating
normally fails to return signal
• Check indoor-outdoor
for specified length of time.
power-on sequence.
• Check indoor address
setting
Condition 2
Outdoor I / F board
• Check wiring of Indoor-
SW103, Bit4 : ON
outdoor communication
(To switch the check code
wires
detection condition.)
• Check outdoor terminator
resistor setting (SW100,
SW103
Bit 2).
ON
• Check power supply to
indoor unit.
1
2 3
4
(Is power turned on?)
• Check connection of
indoor-outdoor
communication cable.
Display on main remote
• Check connection of
controller.
communication connectors
Indoor units unavailable for
on indoor P.C. board.
indoor / outdoor
• Check connection of
communication. :E04
communication connectors
Indoor units available for
on outdoor P.C. board.
indoor / outdoor
• Check for failure in indoor
communication. : E06
P.C. board.
• Check for failure in outdoor
P.C. board (I/F).
Signal cannot be transmitted
• Check outdoor terminator
from outdoor to indoor units
resistor setting (SW100,
for 30 seconds continuously.
Bit 2).
• Check connection of
indoor-outdoor
communication circuit.
More than one indoor unit
• Check indoor addresses.
are assigned same address.
• Check for any change
made to remote controller
connection (group/
individual) since indoor
address setting.
In two remote controller
• Check remote controller
configuration (including
settings.
wireless), both controllers
• Check remote controller
are set up as master.
P.C. boards.
(Header indoor unit is shut
down with alarm, while
follower indoor units
continue operating.)
Communication cannot be
• Check for failure in
established/maintained upon
indoor P.C. board
turning on of power or
during communication.
• Perform automatic address
• Indoor automatic address
setting is started while
setting again after
automatic address setting
disconnecting
for equipment in other
communication cable to
refrigerant line is in
that refrigerant line.
progress.
• Outdoor automatic
address setting is started
while automatic address
setting for indoor units is in
progress.
Indoor unit cannot be
• Check connection of
detected after indoor
indoor-outdoor
automatic address setting is
communication line.
started.
• Check for trouble in indoor
power supply system.
• Check for noise from other
devices.
• Check for power failure.
• Check for failure in indoor
P.C. board.