Toshiba MMD-UP0721HFP-UL Service Manual page 20

Air-conditioner multi type
Hide thumbs Also See for MMD-UP0721HFP-UL:
Table of Contents

Advertisement

NO.
item
5
Forced Thermo-
The Forced Thermo-OFF will be activated when conditions below are satisfied.
OFF
(1) Outdoor / Suction air temp. (TA)
(2) Outdoor / Suction air temp. (TA) and temperature set by remote controller (Ts)
(3) Temperature of discharge air (TF)
When the Outdoor / Suction air temp. is low, the following controls will be operated.
6
Forced Fan OFF
(1) The fan is forcibly turned off according to the temperature of outdoor ambient
(suction) (TA)
(2) After FAN OFF for 60 minutes, FAN will be ON for 1 minute. If the Forced Fan
OFF will be continued or released depends on the Outdoor / Suction air temp.
(TA) at that time.
<Deactivate condition>
(3) Other deactivate conditions of Forced Fan-OFF
Operation
mode
COOL
HEAT
FAN
When connecting to Super Multi u series: 14°F[-10°C]
When connecting to other models than Super Multi u series: 23°F[-5°C]
Outline of specifications
66.2°F[19°C] (T
COOL
When TA
・   ・   ・
59.0°F[15°C] (T
HEAT
When TA
・   ・   ・
1 : When connecting to Super Multi u series : 14.0°F[-10°C]
(
1)(
When connecting to other models than Super Multi u series 23.0°F[-5°C]
Ts + 5.4°F[+ 3°C] (T
COOL
When TA
・   ・   ・
Ts - 5.4°F[- 3°C] (T
HEAT
When TA
・   ・   ・
37.4°F[3°C] (T
COOL
When TF
・   ・   ・
140°F[60°C] (T
HEAT
When TF
・   ・   ・
COOL
FAN
When TA
・   ・   ・
When TA ≤ 14°F[-10°C] (when connecting to other than Super
HEAT
・   ・   ・
Multi u series, 23°F[-5°C])
COOL
FAN
When TA
・   ・   ・
17.6°F [-8 °C] (when connecting to other than
HEAT
When TA
・   ・   ・
Super Multi u series, 26.6°F[-3°C])
Turn off
Mode setting
Test run mode
[°C]
[-10]
[0]
°F
14
32
14°F[-10°C]
HEAT
c)
α
h) or when TA
α
c)
β
h)
β
c)
γ
h)
γ
41°F[5°C]
44.6°F [7°C]
Outdoor / Suction air temp. °F [°C]
[10]
[20]
[30]
50
68
86
41
TS+5.4°F [+3°C]
FAN
TS-5.4°F [-3°C]
FAN
FAN
- 20 -
Remarks
CODE No. (DN)
T
c : (DN)
α
T
h : (DN)
α
14.0°F[-10°C]
T
c : (DN)
β
T
h : (DN)
β
T
c : (DN)
γ
T
h : (DN)
γ
OPERATION STANDBY
is displayed
[40]
[50]
104
122
COOL
109
402
=0019
403
=0015
404
=0003
405
=0003
406
=0003
407
=0060