Toshiba MMD-UP0721HFP-UL Service Manual page 107

Air-conditioner multi type
Hide thumbs Also See for MMD-UP0721HFP-UL:
Table of Contents

Advertisement

Table 1.Setting data(CODE No. table(example))
DN
Filter display delay timer
01
Dirty state of filter
02
Central control address
03
Specific indoor unit priority
04
Heating suction temperature shift
06
Automatic mode
0D
Cooling only
0F
Type
10
Indoor unit capacity
11
Line address
12
Indoor unit address
13
Group address
14
Automatic restart of power failure
28
Selection of option / Trouble input
2A
(TCB-PCUC2E: CN3)
HA terminal (CN61) select
2E
Ventilating fan control
31
Sensor SW
32
Temperature unit select
33
External static pressure
5D
Timer setting (wired remote controller)
60
Fan OFF control during defrosting
72
Alram output setup of the header unit
79
Change unit 0.9°F(0.5°C) or 1.8°F(1°C) on remote
7A
Region
E0
Presence of Application control kit
F6
(TCB-PCUC2E)
FC
Communication protocol
1Fb
Remote controller operation
1FC
Indoor unit terminating resistance
402
403
404
405
406
407
Freeze proofing for humidifier and solenoid valve
41B
Forcible OFF control for indoor fan
Table 2. Type : CODE No.10
Setting
Type
data
4-way Air Discharge
*1
0001
Cassette Type
Outside Air Unit
0016
* 1
EEPROM initial value on the P.C. board for indoor unit
servicing.
* 2
CAUTION
< Model name MMD-UP****HFP-UL >
For the above model. Set the CODE no. to
"28"
the setting data "0000" (initial) to "0001"
"33"
the setting data "0000" (initial) to "0001"
"7A" the setting data "0000" (initial) to "0001"
Item
Type name abb.
MMU-UP****HP-UL
MMD-UP****HFP-UL
Setting data
0001 : Enable
0001 : 0.9°F(0.5°C)
Table 3. Indoor unit capacity : CODE No.11
Setup data
Model
*1
0000
Invalid
0021
072 type
0023
096 type
0024
120 type
- 107 -
Factory-set value
0002 : 2500H
0000 : Standard
00Un/0099 : Unfixed
0000 : No priority
0002 : +3.6°F(+2°C)
0001 : No automatic
0000 : Heat pump
Depending on model type
According to capacity type
00Un/0099 : Unfixed
00Un/0099 : Unfixed
00Un/0099 : Unfixed
0000 : None
0002 : None
0000 : Usual (HA terminal)
0000 : Unavailable
0000 : Body sensor
0000 : Default setting
0000 : Available
0001 : OFF
0000 : Not including the state of
following unit
0000 : 1.8°F(1°C)
0000 : Domestic
0000 : None
0000 : TCC-LINK
0000 : Operation possible
0000 : OFF
66.2°F(
)
59°F(
)
37.4°F(
)
37.4°F(3°C)
37.4°F(3°C)
140°F(
)
0000 : Unavailable