Toshiba MMY-MUP0721FT6P-UL Service Manual page 208

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Controller
Check
Sub-code
code
E09
E10
01:
Indoor-outdoor
communication
02:
Outdoor-outdoor
E12
E12
communication
E15
E15
00:
Capacity over
01-:
No. of units
connected
E16
E16
E17
E18
00:
No header unit
02:
Two or more
header units
E19
E19
01:
Connection of
outdoor unit
from other line
E20
E20
02:
Connection of
indoor unit
from other line
Location
Description
System status
of
detection
Remote
Duplicated
Stop of
controller
master remote
corresponding
controller
unit
Indoor unit
Indoor inter-
Stop of
MCU
corresponding
communication
unit
trouble
I/F
Automatic
All stop
address starting
trouble
I/F
Indoor unit not
All stop
found during
automatic
address setting
I/F
Too many
All stop
indoor units
connected
Indoor unit
communication
Stop of
trouble between
corresponding
indoor unit(s)
unit(s)
and FS unit(s)
Indoor unit
Trouble in
Stop of
communication
corresponding
between indoor
unit
header and
follower units
I/F
Trouble in
All stop
number of
outdoor header
units
I/F
Connection to
All stop
other line found
during
automatic
address setting
- 208 -
Check code detection
Check items (locations)
condition(s)
In two remote controller
• Check remote controller
configuration (including
settings.
wireless), both controllers
• Check remote controller
are set up as master.
P.C. boards.
(Header indoor unit is shut
down with alarm, while
follower indoor units
continue operating.)
Communication cannot be
• Check for failure in
established/maintained upon
indoor P.C. board
turning on of power or
during communication.
• Indoor automatic address
• Check whether the outdoor
setting is started while
unit of other systems or the
automatic address setting
indoor unit is connected to
for equipment in other
Uv (U1/U2) line or Uc
refrigerant line is in
(U5/U6) line.
progress.
• Perform automatic address
• Outdoor automatic
setting again after
address setting is started
disconnecting
while automatic address
communication cable to
setting for indoor units is in
that refrigerant line.
progress.
Indoor unit cannot be
• Check connection of
detected after indoor
indoor-outdoor
automatic address setting is
communication line.
started.
• Check for trouble in indoor
power supply system.
• Check for noise from other
devices.
• Check for power failure.
• Check for failure in indoor
P.C. board.
• Combined capacity of
• Check capacities of indoor
indoor units is too large.
units connected.
• Check total capacity of
Note:
indoor units.
If this code comes up
• Check capacity settings of
after backup setting for
outdoor units.
outdoor unit failure is
• Check No. of indoor units
performed, perform "No
connected.
capacity over detected"
• Check for failure in outdoor
P.C. board (I/F).
setting.
<"No capacity over detected"
setting method>
Turn on SW103 / Bit 3 on I/F
P.C. board of outdoor header
unit.
For Cooling Only model,
this check code is not
displayed even if it exceeds
the combined capacity of
indoor units.
• More than 128 indoor units
are connected.
• Check order in which
There is no communication
power was turned on.
from FS unit(s)
• Check indoor unit(s)-FS
unit(s) cable.
• Check FS unit port
address setting of indoor
unit.
Periodic communication
• Check remote controller
between indoor header and
wiring.
follower units cannot be
• Check indoor power supply
maintained.
wiring.
• Check P.C. boards of
indoor units.
• There are more than one
The outdoor unit which
outdoor header units in
turned on SW101 and the
one line.
bit 1 of the interface P.C.
• There is no outdoor header
board is set to Header unit.
unit in one line.
• Check SW101 bit 1 of
follower outdoor unit.
• Check connection of
indoor-outdoor
communication line.
• Check for failure in outdoor
P.C. board (I/F).
Equipment from other line is
Check whether the outdoor
found to have been
unit of other systems or the
connected when indoor
indoor unit is connected to
automatic address setting is
Uv (U1/U2) line or Uc
in progress.
(U5/U6) line.