Toshiba MMY-MUP0721FT6P-UL Service Manual page 207

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Controller
Check
Sub-code
code
No. of indoor
units from
which signal is
received
normally
E06
E04
No. of indoor
units from
which signal is
received
normally
E04/E06
E06
E07
Duplicated
indoor address
E08
E08
Location
Description
System status
of
detection
I/F
Dropping out of
All stop
indoor unit
Indoor unit
Indoor-outdoor
Only specified
communication
indoor units stop
circuit trouble
Indoor unit
Indoor-outdoor
All stop
communication
circuit trouble
(E04)
I/F
Dropping out of
indoor unit
(E06)
I/F
Indoor-outdoor
All stop
communication
circuit trouble
(detected at
outdoor end)
Indoor unit
Duplicated
All stop
I/F
indoor address
- 207 -
Check code detection
Check items (locations)
condition(s)
Condition 1
• Check power supply to
All indoor unit initially
indoor unit.
communicating normally
(Is power turned on?)
fails to return signal for
• Check connection of
specified length of time.
indoor-outdoor
communication cable.
Condition 2
• Check connection of
Outdoor I / F board
communication connectors
SW103, Bit4 : OFF
on indoor P.C. board.
(Factory default)
• Check connection of
communication connectors
on outdoor P.C. board.
• Check for failure in indoor
P.C. board.
• Check for failure in outdoor
P.C. board (I/F).
Condition 1
• Check power supply to
Indoor unit initially
indoor unit.
communicating
(Is power turned on?)
normally fails to return
• Check indoor-outdoor
signal for specified
power-on sequence.
length of time.
• Check indoor address
setting
• Check wiring of Indoor-
outdoor communication
wires
• Check outdoor terminator
resistor setting (SW100,
Bit 2).
• Check power supply to
One indoor unit or more
indoor unit.
initially communicating
(Is power turned on?)
normally fails to return signal
• Check indoor-outdoor
for specified length of time.
power-on sequence.
(detected when power is
• Check indoor address
turned on)
setting
• Check wiring of Indoor-
outdoor communication
wires
• Check outdoor terminator
resistor setting (SW100,
Bit 2).
• Check power supply to
indoor unit.
(Is power turned on?)
Display on main remote
• Check connection of
controller.
indoor-outdoor
Indoor units unavailable for
communication cable.
indoor / outdoor
• Check connection of
communication. :E04
communication connectors
Indoor units available for
on indoor P.C. board.
indoor / outdoor
• Check connection of
communication. : E06
communication connectors
Communication system, if
on outdoor P.C. board.
the termination resistance
• Check for failure in indoor
is not set in any of the
P.C. board.
indoor units.
• Check for failure in outdoor
P.C. board (I/F).
Signal cannot be transmitted
• Check outdoor terminator
from outdoor to indoor units
resistor setting (SW100,
for 30 seconds continuously.
Bit 2).
• Check connection of
indoor-outdoor
communication circuit.
More than one indoor unit
• Check indoor addresses.
are assigned same address.
• Check for any change
made to remote controller
connection (group/
individual) since indoor
address setting.