5.12 Gas conversion
The boiler is designed to operate with methane gas (G20) according to
parameter
.
b
Conversion from a family gas to other family gas can be performed
easily also when the boiler is installed.
b
sonnel.
- Access the technical parameters
- Use key C or D to select the desired option:
b
C
must be carried out (see chap. 5.4). Check that the fan revolutions cor-
respond to what is indicated in tables 1 and 2, par. "5.11 Adjustments".
5.13 Output change (P208)
(range 0 ÷ 1, default 0). In particular:
- access the technical parameters
25 W: 0
confirm
35 W: 1
confirm.
Configure the fan speeds of your boiler as indicated in tables 1 and 2, par.
"5.11 Adjustments".
30 W MODEL
- Access the technical parameters
(35kW)
confirm.
- Change the fan speed as indicated in tables 1 and 2 of your model.
b
the parameters.
5.14 Signalling and faults
If a fault is present, the icon
0.5sec OFF, the backlight blinks for 1min at a frequency of 1sec ON and
1sec OFF, after which it switches off, while the bell continues to flash.
The error code appears on the 4 digits of the display.
When a fault occurs, the following icons may appear:
-
- RESET lights up for an alarm that needs to be manually reset by the
)
-
lights up along with the
water failure faults
-
lights up in the presence of water pressure alarms or warnings, in
which case the water pressure value is displayed as an alternative to
the fault code every 3 seconds.
Reset function
To restore boiler operation in the event of a fault, the boiler must be
operated by pressing the RESET button.
P2
.
" procedure
GAC
P2
P2
blinks at a frequency of 0.5sec ON and
)
>2 sec
At this point, if the correct operating conditions have been restored,
the boiler will restart automatically. Up to a maximum of 5 consecutive
attempts to unlock the same alarm from the interface are possible,
after which the error code E099 appears on the display.
-
confirm.
In this case, the boiler must be disconnected from the electricity sup-
ply and then reconnected again, to reactivate operation.
b
If the reset attempts do not activate the boiler, contact the Techni-
cal Assistance Centre.
Fault E041
Should the pressure value fall below the safety value of 0.3 bar, the boiler
displays the fault code E041 for a transitory time of 10 min.
E040 is displayed.
:
With a boiler in fault E040:
check that the pressure value reaches 1-1.5 bar by means of a hy-
1
drometer located under the shelf or by accessing the INFO menu ("6.3
INFO menu", item I018)
clo
to restore operation.
Once operation is restored, the boiler performs an automatic vent cycle as
described in paragraph "4.10 Filling the heating system and removing air".
b
If the drop in pressure is very frequent, request the intervention of
the Technical Assistance Centre.
Fault E060
The boiler is working normally, but does not guarantee the stability of the
DHW temperature that is, however, supplied at a temperature of around
50°C. Intervention of the Technical Assistance Centre is required.
Fault E091
The boiler has an auto-diagnostic system which, based on the total num-
ber of hours in certain operating conditions, can signal the need to clean
the primary exchanger (alarm code E091).
Once the cleaning operation has been completed, reset to zero the total
hour meter with special kit supplied as an accessory following procedure
indicated below:
access the technical parameters
confirm.
NOTE: The meter resetting procedure should be carried out after each
in-depth cleaning of the primary heat exchanger or if it is replaced.
The fault E091 occurs when the hour counter exceeds 2500 hours; this
access the INFO menu
probe hour counter (display/100, example 2500h = 25).
16
A) by turning it anticlockwise
A) making sure you hear the mechanical click.
A
P3
as follows:
I015 to display the val