Riello DB 6 LSE C13 Installation, Use And Maintenance Instructions page 18

Light oil/gas dual fuel industrial burners
Table of Contents

Advertisement

Technical data
LMV52... basic unit
Mains voltage
Mains frequency
Power consumption
Safety class
Terminal loading
Unit fuse F1 (internally)
'Inputs'
Perm. mains primary fuse (externally)
Undervoltage
Safety shutdown from operating
at mains voltage
• Restart on rise in mains voltage
Oil pump / magnetic clutch (nominal voltage)
• Nominal current
• Output factor
Air pressure switch test valve (nominal voltage)
• Nominal current
• Output factor
Terminal loading
Total contact loading:
'
Outputs
'
• Mains voltage
• Input current of unit (safety loop) total
load on contacts resulting from:
- Fan motor contactor
- Ignition transformer
- Valve
- Oil pump / magnetic clutch
Single contact loading:
Fan motor contactor (nominal voltage)
• Nominal current
• Output factor
Alarm output (nominal voltage)
• Nominal current
• Output factor
Ignition transformer (nominal voltage)
• Nominal current
• Output factor
Fuel valve gas (nominal voltage)
• Nominal current
• Output factor
Fuel valve oil (nominal voltage)
• Nominal current
• Output factor
Cable lengths
Main line
Environmental
Operation
conditions
Climatic conditions
Mechanical conditions
Temperature range
Humidity
5
CHAPTER
AC 230 V -15 % / +10 %
50 / 60 Hz ±6 %
< 30 W (typically)
I, with parts according to II and III to DIN EN 60730-1
6.3 AT
Max. 16 AT
position
< AC 186 V
> AC 188 V
2A
cosj > 0.4
0.5A
cosj > 0.4
AC 230 V -15 % / +10 %
Max. 5 A
1A
cosj > 0.4
1A
cosj > 0.4
2A
cosj > 0.2
2A
cosj > 0.4
1A
cosj > 0.4
Max. 100 m (100 pF/m)
DIN EN 60721-3-3
class 3K3
class 3M3
-20...+60 °C
< 95 % r.h.