5.2
Gas train - pilot connection
The burner is fitted with a dedicated gas train that is fixed to the pipe coupling.
It should be connected to the main train downstream the filter or the pressure regulator (depending on configuration).
Oil burners (with LPG pilot) can be directly connected to the LPG cylinder.
Attention: Gas supply pressure 68 - 500 mbar.
1
5.3
Ignition pilot
For proper operation, adjust gas pressure (measured at pressure test point) to 16 mbar (7.3 Nm
Check pilot flame stability before starting up the main burner.
In case of ignition problems, verify:
the correct positioning of the ignition electrode;
the gas pressure according to the indications.
14
CHAPTER
D9266EV
Fig. 18
5
Preparation for start up
3
/h).