Download Print this page

Johnson Controls MP8 20 Series Manual page 2

Pneumatic valve-actuator

Advertisement

2
Additional equipment
• Hand wheel
• Pneumatic positioner
• (2) end position indicators + 2kΩ-feedback potentiometer
Storage:
• Storage temperature -4°C to +80°C, dry and free of dirt.
• Do not damage the lacquer. The lacquer is a foundation intended only as a protection against corrosion
while in storage and during transport.
• In rooms where moisture or condensation are present use heating or a drying agent to maintain a
moisture-free atmosphere.
Transport:
• Transport temperature -4°C to +80°C.
• Protect against external forces (shock, vibration etc.).
• Do not damage the protective lacquer.
Diaphragm
Stroke
2
Area (cm
)
(mm)
160
13
Air supply connection:
The diaphragm actuator is equipped with a tube connection permitting connection with 4 x 6-mm plastic
tubing.
Mounting orientation
It is recommended that the valves be mounted
within 90° of the upright position, in an easily
accessible location.
Caution:
When mounting in an inclined to
horizontal
should be fitted such that the
stanchions are aligned vertically
one above the other as is
depicted.
A
18
Spring range
Spring close-off
(kPa)
force (N)
20 – 50
60 – 90
Caution:
Remember to take tubing temperature limits into account.
position,
the
yoke
Air pressure (kPa) to close-off force (N)
120
320
1120
960
480
90° Max.
111 6138 050 E
140
1440
1760
800
1120
O.K.
Stanchions
160

Advertisement

loading

This manual is also suitable for:

Mp8000