Download Print this page

Johnson Controls MP8 20 Series Manual page 11

Pneumatic valve-actuator

Advertisement

Close-off Pressures [kPa] with VG Valves
Diverting: Inlet – Outlet 2 (Bypass)
K
vs
DN
Actuator
Coefficient
VG8000N PN 16 Valves
15
4.0 + 2.5
15
0.1 – 1.6
20
4.0 / 6.3
MP8x2
25
6.3 / 10
32
10 / 16
40
16 / 25
VG8300N PN 16 Valves
40
16 / 25
MP8x2
VG8000H PN 25 Valves
15
4.0 + 2.5
15
0.1 – 1.6
20
4.0 / 6.3
MP8x2
25
6.3 / 10
32
10 / 16
40
16 / 25
VG8300H PN 25 Valves
40
16 / 25
MP8x2
DA Actuator
Spring-return up
PDTO Valve
Mixing: Inlet 1 – Outlet
RA Actuator
Spring-return down
PDTC Valve
Mixing: Inlet 2 – Outlet
Diverting: Inlet – Outlet 2 (2-way)
Spring Range
[kPa]
20 - 50
60 - 90
Spring ID No.
23
63
600
1600
1600
1600
200
1600
90
1600
-
1000
-
580
-
1600
30
2500
820
2500
-
2500
-
1780
-
880
-
510
-
2500
DA Actuator
Air Pressure closes
PDTO Valve
Mixing: Inlet 1 – Outlet
Diverting: Inlet – Outlet 2 (Bypass)
RA Actuator
Air Pressure closes
PDTC Valve
Mixing: Inlet 2 – Outlet
Diverting: Inlet – Outlet 2 (2-way)
120 kPa
140 kPa
Spring Range
Spring Range
[kPa]
20 - 50
60 - 90
20 - 50
Spring ID No.
Spring ID No.
23
63
23
1600
1600
1600
1600
1600
1600
1600
890
1600
1600
560
1600
1250
230
1600
740
100
1060
1600
1600
1600
2500
1330
2500
2500
2500
2500
2500
590
2500
2250
350
2500
1140
120
1650
670
30
990
2500
2500
2500
160 kPa
Spring Range
[kPa]
[kPa]
60 - 90
20 - 50
60 - 90
Spring ID No.
63
23
1600
1600
1600
1600
1600
1600
1600
1600
1600
1510
1600
1600
740
1600
1250
420
1380
1600
1600
1600
2500
2500
2500
2500
2500
2500
1940
2500
2500
1300
2500
2250
630
2160
1140
350
1320
2500
2500
2500
63
740
670

Advertisement

loading

This manual is also suitable for:

Mp8000