BMS
Description
Address
22
Superheat valve Comp 4
23
Control Temperature
24
Outside Air Temperature
25
Entering water temperature
26
Leaving water temperature
Condenser temperature (either
27
from NTC or P-T)
28
Current entering water Setpoint
Active Proportional Band for
29
compressor
30
Water Setpoint
31
Dead band
32
Proportional Band for compressor
33
Entering water temperature 2
34
Leaving water temperature 2
35
Storage tank water temperature
Building Supply water temperature
36
(Flow)
Default
Category UOM
Min
0
Default
---
-72.0
0
Default
°C
-99.9
0
Default
BAR
-99.9
0
Default
°C
-99.9
0
Default
°C
-99.9
0
Default
---
-99.9
22.0
Default
°C
1.5
Default
°C
22.0
Default
°C
1.0
Default
°C
1.5
Default
°C
0
Default
°C
-99.9
0
Default
°C
-99.9
0
Default
°C
-99.9
0
Default
°C
-99.9
80
Max
Read/Write
324.0
R
99.9
R
99.9
R
99.9
R
99.9
R
99.9
R
0
45.0
R
0
9.9
R
5.0
45.0
R/W
0
9.9
R/W
0
25.0
R/W
99.9
R
99.9
R
99.9
R
99.9
R
Variable name
Superheat_C4
Ctrl_temp
OAT
EW_temp
LW_temp
Cond_temp
Active_Setpoint
Active_Pro_band
Setpoint
D_Band
Pro_band
EW_temp2
LW_temp2
Tank_temp
Bld_Supply_temp