8.1 Four-Lead Reconnection

The following drawings illustrate the reconnection of
four-lead generator sets. In all cases, conform to the
National Electrical Code (NEC).
NOTICE
Voltage reconnection. Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.
100- -120-Volt Configurations
If the installation requires a factory two-pole circuit
breaker, do not connect the load-side terminals of the
circuit breaker.
See Figure 8-1.
requires a 100--120-volt, 2-wire system, use a
single-pole circuit breaker.
connecting stator phase leads together, size the output
lead (L1) to handle the amperage. Use a jumper lead on
the line side of the circuit breaker to balance the load of
the generator set.
L0 (Neutral)
Ground
Load
Side
Line
Side
4
3
2
1
Figure 8-1 100--120-Volt, 3-Wire Configuration
26 Reconnection/Adjustments
If the installation
See Figure 8-2.
When
L0
GRD.
L1
L2
Two-Pole
Circuit
Breaker
Jumper
Lead
100- -120/200- -240-Volt Configurations
The 100--120/200--240-volt configuration does not use
a jumper lead. If the unit was originally wired for straight
100--120 volt, 3 wire, remove the jumper lead (see
Figure 8-1 for location).
breaker. Application of two single-pole circuit breakers
does not conform to NEC requirements for supplying a
200--240 volt
load—even
mechanically attached.
different phases—never connect them.
L0 (Neutral)
Ground
Load
Side
Line
Side
4
3
2
1
Stator Leads
L0--L1
L0--L2
Figure 8-2 100--120-Volt, 2-Wire Configuration
L0 (Neutral)
Ground
Load
Side
Line
Side
4
3
2
1
Stator Leads
L0--L1
L0--L2
L1--L2
Figure 8-3 100--120/200--240-Volt,
3-Wire Configuration
Select a two-pole circuit
if
the
breakers
Leads L1 and L2 are for
L0
GRD.
L1
Single-Pole
Circuit
Breaker
60 Hz
100--120 Volt
100--120 Volt
L0
GRD.
L2
L1
Factory
Two-Pole
Circuit
Breaker
100- -120/200- -240 Volt,
3 Wire
60 Hz
100--120 Volt
100--120 Volt
200--240 Volt
TP-6335
are
9/04