Discharge Air Control; Sylk Calibration Offsets - Honeywell TC300 Integration Manual

Bacnet integration guide
Hide thumbs Also See for TC300:
Table of Contents

Advertisement

Discharge air control

Name
Cfg_FanCoilSupTempHtgSp
Cfg_FanCoilSupTempClgSp
Cfg_FanCoilDATSpEnSwitch
Cfg_FanCoilDATHeatOffset
Cfg_FanCoilDATCoolOffset
Cfg_DaT_Ctrl_Cool_Tr
Cfg_DaT_Ctrl_Cool_It
Cfg_DaT_Ctrl_Heat_Tr
Cfg_DaT_Ctrl_Heat_It

Sylk calibration offsets

Name
Cfg_LocalSensCalOffset
_Temp
Cfg_LocalSensCalOffset
_Hum
Cfg_SylkCalOffset_Sylk
Bus2Temp
Cfg_SylkCalOffset_Sylk
Bus2RH
Cfg_SylkCalOffset_Sylk
Bus2CO2
Cfg_SylkCalOffset_Sylk
Bus3Temp
Cfg_SylkCalOffset_Sylk
Bus4Temp
64
Table 29 Discharge air control
BACnet
BACnet
Object
Object
Type
Instance
Analog
1723
Value
Analog
1724
Value
Binary
454
Value
Analog
2009
Value
Analog
2010
Value
Analog
2011
Value
Analog
2012
Value
Analog
2014
Value
Analog
2015
Value
Table 30 Sylk calibration offsets
BACnet
BACnet
Object
Object
Type
Instance
Analog
23
Value
Analog
103
Value
Analog
24
Value
Analog
25
Value
Analog
100
Value
Analog
26
Value
Analog
27
Value
Default
Range
Value
85 °F
75 to 180 °F
55 °F
40 to 80 °F
0
Off=0,
On=1
Δ°F
Δ°F
0
0 to 90
Δ°F
Δ°F
0
0 to 40
Δ°F
Δ°F
6
0 to 30
300
0 to 5000
seconds
seconds
Δ°F
Δ°F
6
0 to 30
300
0 to 5000
seconds
seconds
Default
Range
Value
0 °F
-10 to 10 °F
0%RH
-10 to 10%RH
0 °F
-10 to 10 °F
0%RH
-10 to 10%RH
0 °F
-100 to 100 ppm
0 °F
-10 to 10 °F
0 °F
-10 to 10 °F
Description
Discharge air control
maximum heating setpoint.
Discharge air control
minimum cooling setpoint.
Discharge air control enable
flag
Discharge air control heating
initial offset
Discharge air control cooling
initial offset
Discharge air control cooling
throttling range
Discharge air control cooling
integral time
Discharge air control heating
throttling range
Discharge air control heating
integral time
Description
Local onboard temperature
sensor calibration offset
Local onboard humidity
sensor calibration offset
TR40_2/ TR-21
temperature calibration
offset
TR40_2 humidity calibration
offset
TR40_2 CO2 calibration
offset
TR40_3 temperature
calibration offset
TR40_4 temperature
calibration offset
Discharge air control

Advertisement

Table of Contents
loading