Selecting Discharge and Return Air
Temperature Sensor Mounting
Locations
Refer to the guidelines below and Fig. 8–12 for mounting
locations of the Discharge and Return Air Temperature
Sensors.
Selecting Discharge Air Temperature
Sensor Mounting Location
1. Mount the Discharge Air Temperature Sensor on the
supply duct in a location where the air is mixed well.
Mount the Discharge Air Temperature Sensor out of sight
of the A-Coil/Heat Exchanger when possible. See Fig. 8.
2. When possible, mount the Discharge Air Temperature
Sensor upstream of a Steam Humidifier, a Fan Powered
Humidifier or a Dehumidifier that is ducted to the supply.
See Fig. 9–10.
3. If space does not allow a Discharge Air Temperature
Sensor upstream of a Steam Humidifier or Fan Powered
Humidifier, mount the Discharge Air Temperature Sensor
downstream of the Humidifier. See Fig. 9.
4. If a Bypass Humidifier is installed, mount the Discharge
Air Temperature Sensor downstream of the Bypass
Humidifier. See Fig. 11–12.
Selecting Return Air Temperature Sensor
Mounting Location
1. Install the Return Air Temperature Sensor on the return
duct in a location where the air is mixed well. Mount the
Return Air Temperature Sensor downstream of a Bypass
Humidifier, Dehumidifier or Ventilator. See Fig. 8–12.
MOUNT DISCHARGE
SENSOR HERE
VENTILATOR
OR
DEHUMIDIFIER
MOUNT RETURN
SENSOR HERE
DOWNSTREAM OF
VENTILATOR OR
DEHUMIDIFIER
A-COIL
HEAT
EXCHANGER
BLOWER
M33074
Fig. 8.
ALTERNATE MOUNTING LOCATION
FOR DISCHARGE SENSOR.
VENTILATOR
OR
DEHUMIDIFIER
MOUNT RETURN
SENSOR HERE
DOWNSTREAM OF
VENTILATOR OR
DEHUMIDIFIER
ALTERNATE MOUNTING LOCATION
FOR DISCHARGE SENSOR.
DEHUMIDIFIER
MOUNT RETURN
SENSOR HERE
DOWNSTREAM OF
DEHUMIDIFIER
9
®
VISIONPRO
8000 WITH REDLINK™
STEAM OR
FAN
POWERED
HUMIDIFIER
MOUNT
DISCHARGE
SENSOR HERE
ABOVE CENTER
OF A-COIL
UPSTREAM OF
HEAT
STEAM OR FAN
EXCHANGER
POWERED
HUMIDIFIER
BLOWER
Fig. 9.
MOUNT
DISCHARGE
SENSOR HERE
ABOVE CENTER
OF A-COIL
UPSTREAM OF
DEHUMIDIFIER
HEAT
EXCHANGER
BLOWER
Fig. 10.
M34806
M34807
68-0312—03