Alerts

Name
AlarmPriority_ProofofAirFlow
AlarmPriority_SpaceFreezeProt
ect
AlarmPriority_UnknownTime
AlarmPriority_TempSens
36
Table 8 Alerts
BACnet
BACnet
Object
Object
Type
Instance
Binary
2002
Value
Binary
2049
Value
Binary
2050
Value
Analog
2081
Value
Range
Inactive=0,
Active=1
Inactive=0,
Active=1
Inactive=0,
Active=1
{BIT0=INACTIVE,
BIT1=HIGH,
BIT2=MEDIUMN_ONBOARD,
BIT3=MEDIUMN_REMOTE,
BIT4=MEDIUMN_SYLK}
Description
Supply fan status
mismatch alarm & priority.
If space temperature has
dropped below 43 ℉ and
after 120 seconds of
delay, high priority alarm is
created.
Time lost alarm
High Priority:
1. Only local sensor
configured & even if any
one of the on-board
temperature sensors is in
alarm
2. Only Remote sensor
configured & TR40 sensor
connected to Sylk address
2 is giving null value.
3. Configured as multi
sensor & both the remote
sensor & on-board
configured sensor has
failed.
Medium priority:
1. Configured as Multi
sensor & only the on-
board sensor has failed.
but getting reliable value
from the Sylk sensors.
2. Configured as multi
sensor & only one of the
Sylk sensor has failed with
values available from
other Sylk sensors (If
configured) or on-board
sensor.
When a valid network
temperature is available,
then the high priority
alarms will be considered
as medium priority alarm.