Gas Piping Pressure Test - Viessmann WB2B 45 Installation Instructions Manual

Hide thumbs Also See for WB2B 45:
Table of Contents

Advertisement

Boiler Connections
Connections
(continued)

Gas piping pressure test

When performing the gas piping pressure test, ensure the following requirements are met.
18
WARNING
Never check for gas leaks with an
open flame.
WARNING
Exposing boiler gas pressure
regulator and gas valve to extreme
pressures renders warranty null and
void.
IMPORTANT
½ psig = 14 "w.c.
1. Isolate the boiler from the gas supply
piping system using the individual
manual shutoff valve during pressure
tests equal to or less than ½ psig/
14 "w.c.
2. The boiler and its individual shutoff
valve must be disconnected from the
gas supply piping system during any
pressure testing of that system at
test pressures in excess of
½ psig/14 "w.c.
3. Perform leak test.
Use approved liquid spray solution
for bubble test. Ensure that no liquid
is sprayed on any electrical
components, wires or connectors.
Do not allow leak detection fluid to
contact gas valve regulator or
regulator vent opening.
4. Correct any and all deficiencies.
5. Remove air from gas line.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 200-wWb2b 60

Table of Contents