Gas Piping Pressure Test; Heating Water Connections - Viessmann B2HA 80 Installation Instructions Manual

Hide thumbs Also See for B2HA 80:
Table of Contents

Advertisement

Boiler Connections
Connections
(continued)

Gas piping pressure test

When performing the gas piping pressure test, ensure the
following requirements are met.
WARNING
Never check for gas leaks with an open flame.
WARNING
Exposing boiler gas pressure regulator and gas valve to
extreme pressures renders warranty null and void.
IMPORTANT
½ psig = 14 "w.c.
1. Isolate the boiler from the gas supply piping system
using the individual manual shutoff valve during
pressure tests equal to or less than ½ psig (14 "w.c.)
2. The boiler and its individual shutoff valve must be
disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures in excess of ½ psig (14 "w.c.)
3. Perform leak test.
Use approved liquid spray solution for bubble test.
Ensure that no liquid is sprayed on any electrical
components, wires or connectors. Do not allow
leak detection fluid to contact gas valve regulator
or regulator vent opening.
4. Correct any and all deficiencies.
5. Remove air from gas line.
20
Vitodens 200-W B2HA 80 to 100, 285 to 352 Installation

Heating water connections

1. Thoroughly flush heating system (particularly before
connecting the boiler to an existing system).
2. Connect boiler to the heating system.
WARNING
Exposing the boiler to pressures and temperatures in
excess of those listed will result in damages, and will
render warranty null and void.
Max. allowable working pressure (MAWP)..4 bar (60 psig)
Max. boiler water temperature.....................210ºF (99ºC)
3. Connect field supplied nipples and tees as shown
for DHW supply and return.
Legend
DR Boiler heating return for domestic hot water production
DS Boiler heating supply for domestic hot water production
BD Boiler Drain
BF Boiler Fill
BR Boiler Return
BS Boiler Supply
GC Gas Connection
PRV Pressure Relief Valve
*1 See page 43 for alternate DHW connection.
IMPORTANT
Apply sufficient amount of thread sealant (supplied) when
making the connections.
*1 DHW
Connections
(Field Supplied)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 200-wB2ha 285B2ha 88B2ha 311B2ha 100B2ha 352

Table of Contents