DRIVE-CLiQ interfaces X100 - X103
Table 12-4
Characteristic
Connector type
Cable type
Max. cable length
Table 12-5
Pin assignment, X100 - X103
 
Pin
 
1
 
2
 
3
4
5
6
7
8
A
B
DRIVE-CLiQ topology
NX components can be connected to the NCU via DRIVE-CLiQ. The following rules apply for the
wiring:
• Only one star topology is permitted between the NX and the NCU. In this way, only one NX
can be operated per DRIVE-CLiQ port of an NCU.
• DRIVE-CLiQ ports not assigned to NX can be wired to other DRIVE-CLiQ components.
• Once an NX has been connected and configured, you cannot simply insert it into a different
DRIVE-CLiQ port, as the addresses of the integrated drives are set permanently from the point
of view of the PLC. The following table illustrates this relation:
Table 12-6
DRIVE-CLiQ port on the NCU
X105
X104
X103
X102
X101
The following figure shows a sample topology:
NCU 1750
Equipment Manual, 10/2023, A5E45627807B AH
Characteristics of X100 - X103
Version
DRIVE-CLiQ connector
DRIVE-CLiQ standard (inside the control cabinet)
MOTION-CONNECT (outside the control cabinet)
70 m
Signal name
TXP
TXN
RXP
-
-
RXN
-
-
+ (24 V)
M (0 V)
NX PROFIBUS addresses
Technical specifications
Transmit data +
Transmit data -
Receive data +
Reserved, do not use
Reserved, do not use
Receive data -
Reserved, do not use
Reserved, do not use
Power supply
Ground
Drive PROFIBUS addresses
15
14
13
12
11
Connectable components
12.1 NX10.3/NX15.3
107