Toshiba MMD-UP0481HFP-UL Service Manual page 76

Hide thumbs Also See for MMD-UP0481HFP-UL:
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
Detected indoor
address
P10
P10
P11
P12
P13
P13
01: TS condition
P15
P15
02: TD condition
Location
Description
System status
of
detection
Indoor unit
Indoor overflow
All stop
trouble
I/F
Outdoor heat
All stop
exchanger
freeze trouble
Indoor unit
Indoor fan
Stop of
motor trouble
corresponding
unit
I/F
Outdoor liquid
All stop
backflow
detection
trouble
I/F
Gas leak
All stop
detection
(TS1 condition)
I/F
Gas leak
All stop
detection
(TD condition)
- 76 -
Check code detection
Check items (locations)
condition(s)
• Float switch operates.
• Check float switch
• Float switch circuit is
connector.
open-circuited or
• Check operation of drain
disconnected at connector.
pump.
• Check drain pump circuit.
• Check drain pipe for
clogging.
• Check for failure in indoor
P.C. board.
• Check shortage of
• Outdoor heat exchanger
remaining frost detection
refrigerant.
has occurred eight times
• Check connection of TE1,
or more due to abnormal
TE2 and TE3 sensors.
frost formation in heating
• Check resistance
operation.
characteristics of TE1,
TE2, and TE3 sensors.
• Check disconnection of
TS1 sensor.
• Check resistance
characteristics of TS1
sensor.
• Check outdoor I/F P.C.
board malfunction.
• Check operation of 4 way
valve.
• Check operation of outdoor
PMV (1, 2, 3).
• Check short circuit from
outlet air to inlet air.
• Motor speed
• Check connection of fan
measurements
connector and wiring.
• Check for failure in fan
continuously
deviate from target
motor.
value.
• Check for failure in indoor
• Overcurrent
P.C. board.
protection is
• Check impact of outside air
activated.
treatment (OA).
<During cooling operation>
• Check full-close operation
When system is in cooling
of outdoor PMV (1, 2, 3, 4).
operation, high pressure is
• Check for failure in Pd or
detected in the unit that
Ps sensor.
has been turned off.
• Check failure in outdoor
P.C. board (I/F).
<During heating operation>
• Check capillary of oil
When system is in heating
separator oil return circuit
operation, low pressure is
for clogging.
detected to be high in unit
• Check for leakage of check
that has been turned off.
valve in discharge pipe
Protective shutdown due to
• Check for insufficiency in
sustained suction
refrigerant quantity.
• Check outdoor service
temperature at or above
judgment criterion
valves (gas side, liquid
for at least 10 minutes is
side) to confirm full
repeated four times or more.
opening.
<TS trouble judgment criterion>
• Check PMVs (PMV1, 2, 3,
In cooling operation: 60 ˚C
4) for clogging.
In heating operation: 40 ˚C
• Check resistance
characteristics of TS1
sensor.
• Check for failure in 4-way
valve.
• Check SV4 circuit for
leakage
Protective shutdown due to
• Check for insufficiency in
sustained discharge
refrigerant quantity.
temperature (TD1 or TD2)
• Check PMVs (PMV 1, 2, 3,
at or above 108 ˚C for at
4) for clogging.
least 10 minutes is repeated
• Check resistance
four times or more.
characteristics of TD1 and
TD2 sensors.
• Check indoor filter for
clogging.
• Check piping for clogging.
• Check SV4 circuit (for
leakage or coil installation
trouble).