Type
CODE No. (DN) "10"
Setting data
Outside Air Unit
0016
1: Default value stored in EEPROM mounted on service board
※
■ How to set fan operation during defrosting
Since the air conditioner for outside air processing gives priority to the introduction of outside air, the fan operation can be set even
during defrosting.
Set the CODE No. (DN) "72"=0000 (fan ON when defrosting).
Set the CODE No. (DN) "9B"=0002 (no hot start control).
■ How to All Fresh Air Intake Unit connect setting
(Case of SMMS-e series)
When only Fresh Air Intake Units connected to Outdoor unit, set the all Fresh Air Intake Unit connection setting at Fresh Air Intake Units.
Set DN data is below :-
Type
MMD-UP***HFP-UL
DN
C8
AE
AF
NOTE : Firstly, set up CODE No. (DN) "C8", then change other two CODEs.
Model
SET DATA
0000
0016
0010
- 37 -
Indoor unit capacity
CODE No. (DN) " 11 "
Setup data
Ability rank
0000
Invalid
※
048 type
0017
1: Default value stored in EEPROM
※
mounted on service board