[Control items]
Function
Manual prohibition release
Card Input 1
(Manual operation)
Manual prohibition release
Card Input 2
(Automatic operation)
Operation status continues
(Do nothing)
Card Input 3
Manual prohibition release
(The status returns to operating condition before
Card Input 4
removing the card.)
1) To change a setting temperature by changing data at
DN code No. 172 to 173.
2) The operation mode can be set by changing data
(0000, 0001, 0002) at DN code No. 16B.
0000: operation mode is the same at the current mode.
(factory setting default)
0001: operation mode returns to the previous mode when
card was inserted. (in case of the previous mode is
Card Input 5
off operation, the operation mode is also off.)
0002: operation mode starts at the same previous mode
when the card was inserted. (the operation mode
is on operation even the previous mode is off
operation.)
See contents below for DN settings and detailed
operations.
* For the card switch box that does not involve contact operation described above, convert signals with a relay including a
normally-closed contact.
[Card input setup.5 Code (DN)]
DN
Item
16C Open mode Set temp. (Cool, Dry)
16D Open mode Set temp. (Heat)
16E Open mode Set temp. (Auto)
170 Open mode Wind direction (Cool, Dry, Fan)
171 Open mode Wind direction (Heat)
172 Close mode Set temp. (Cool, Dry)
173 Close mode Set temp. (Heat)
174 Close mode Set temp. (Auto)
Close (Status that card is inserted)
-0015 5ºF(-15ºC) to 0060 140ºF(60ºC)
-0015 5ºF(-15ºC) to 0060 140ºF(60ºC)
-0015 5ºF(-15ºC) to 0060 140ºF(60ºC)
0000 No change
0000 No change
0004 F4
-0015 5ºF(-15ºC) to 0060 140ºF(60ºC)
-0015 5ºF(-15ºC) to 0060 140ºF(60ºC)
-0015 5ºF(-15ºC) to 0060 140ºF(60ºC)
External contact terminal
Open (Status that card is taken out)
Manual prohibition
(Operation stop)
Manual prohibition
(Operation stop)
Operation status continues and setting temperature
changes
(COOL/DRY: 84.2ºF(29ºC), HEAT: 64.4ºF(18ºC))
Manual prohibition
(Operation stop)
1) To change a setting temperature, fan speed and wind
direction by changing data at DN code No. 16C to 16D.
2) The operation mode can be set by changing data
(0000, 0001) at DN code No. 16A.
0000: operation mode is the same at the current mode.
(factory setting default)
0001: operation automatically starts.
See contents below for DN settings and detailed
operations.
Description
0001 F1
0002 F2
0001 F1
0002 F2
0005 F5
- 41 -
At shipment
0018 64.4ºF(18ºC)
0025 77ºF(25ºC)
No function
No function
0003 F3
0003 F3
No function
0018 64.4ºF(18ºC)
0025 77ºF(25ºC)
No function