Start-up and Shutdown

Stopped to Starting

The following diagram shows the timing from a stopped
mode to energizing the first compressor. The shortest
allowable time would be under the following conditions:
No motor restart inhibit time left from subsequent starts
Figure 30. Sequence of events: stopped to starting
Auto Mode commanded
Auto Mode commanded
by Front Panel or BAS
by Front Panel or BAS
Stopped
Stopped
Stop
Stop
Stop
Or Run
Or Run
Inhibit
Inhibit
Confirm Evaporator Water Flow
Confirm Evaporator Water Flow
(6 Second Filter)
(6 Second Filter)
84
Auto
Auto
Auto
Enforce Restart Inhibit Timer
Enforce Restart Inhibit Timer
(0 to 1 minute)
(0 to 1 minute)
Energize Evaporator
Energize Evaporator
Water Pump Relay
Water Pump Relay
Confirm Evaporator Water
Confirm Evaporator Water
Confirm Evaporator Water
Flow Within 20 minutes
Flow Within 20 minutes
Flow Within 20 minutes
(6 Second Filter)
(6 Second Filter)
(6 Second Filter)
EXV remains closed
EXV remains closed
Oil Heaters Energized
when all Compressors on
Circuit are De-energized
Evaporator water flow occurs quickly with pump on
command
Need to cool (differential to start) already exists
The above conditions would allow a compressor to start in
about 20 seconds.
Call for
Call for
Cooling**
Cooling**
(Differential to Start is met)
(Differential to Start is met)
Waiting
Waiting
Waiting
Auto
Auto
Auto
To Start
To Start
To Start
Wait for Need
Wait for Need
Confirm
Confirm
To Cool
To Cool
Presence of Oil
Presence of Oil
(Diff to Start)
(Diff to Start)
(0 to 90 seconds)
(0 to 90 seconds)
Confirm Presence
Confirm Presence
Confirm Presence
Confirm Presence
of Oil Within
of Oil Within
of Oil Within
of Oil Within
90 Seconds
90 Seconds
90 Seconds
90 Seconds
*
*
Lead Compressor (and its lead circuit) is determined by staging algorithm –
Lead Compressor (and its lead circuit) is determined by staging algorithm –
"Balanced", "Circuit 1 Lead", or "Circuit 2 Lead" selection – also influenced
"Balanced", "Circuit 1 Lead", or "Circuit 2 Lead" selection – also influenced
by lockouts, restart inhibit, or diagnostics present.
by lockouts, restart inhibit, or diagnostics present.
On a manifolded circuit, GP4 will be the first to start and last to stop; GP2 will
On a manifolded circuit, GP4 will be the first to start and last to stop; GP2 will
not run by itself.
not run by itself.
**Note: If Free Cooling is active, it will be the first stage of cooling to stage on.
**Note: If Free Cooling is active, it will be the first stage of cooling to stage on.
Waiting
Waiting
Waiting
To Start
To Start
To Start
Fans pre-start, EXV
Fans pre-start, EXV
moving to
moving to
Send Start Command
Send Start Command
Preposition
Preposition
to Lead
to Lead
0 to 25 Seconds,
0 to 25 Seconds,
Compressor Delay Time
Compressor Delay Time
has expired
has expired
Pre-Position EXV of
Pre-Position EXV of
Pre-Position EXV of
Lead Circuit
Lead Circuit
Lead Circuit
Check Evap Pressure for
Check Evap Pressure for
Check Evap Pressure for
Check Evap Pressure for
Low Pressure Cutout
Low Pressure Cutout
Low Pressure Cutout
Low Pressure Cutout
Transition to
Transition to
Running
Running
Compressor*
Compressor*
Start Control of
Start Control of
Condenser Fan Flow
Condenser Fan Flow
AC-SVX003A-EN