Unit Startup; Pre-Start Quick Checklist; Starting The Unit In Cooling Mode; Heating Cycle - Trane 4YCZ5024F1060A Installation And Operation Manual

Hide thumbs Also See for 4YCZ5024F1060A:
Table of Contents

Advertisement

Unit Startup

Pre-Start Quick Checklist

☐ Is the unit properly located and level with the
proper clearances? See
Clearances," p.
8.
☐ Is the duct work correctly sized, run, taped,
insulated, and weatherproofed with proper unit
arrangement as shown in the ductwork installation
section?
☐ Is the condensate line properly sized, run, trapped,
and pitched and shown in the Condensate Drain
Piping section?
☐ Is the gas piping correctly sized, run, trapped, and
purged of air? See Gas Piping Installation section.
☐ Is the filter of the correct size and quantity? Is it
clean and in place? See Air Filter Installation
section.
☐ Is the wiring properly sized and run according to the
unit wiring diagram?
☐ Are all the wiring connections, including those in
the unit tight?
☐ Has the unit been properly grounded and fused
with the recommended fuse size?
☐ Is the thermostat well located, level, and correctly
wired? See Electrical Wiring section.
☐ Have the air conditioning systems been checked at
the service ports for charge and leak tested if
necessary?
☐ Do the condenser fan and indoor blower turn free
without rubbing and are they tight on the shafts?
☐ Has the indoor blower speed been determined and
the proper speed been set? To adjust the fan, see
the Indoor Fan Motor Speed Tap Setting section.
☐ Has all work been done in accordance with
applicable local and national codes?
☐ Are all covers and access panels in place to prevent
air loss and safety hazards?
Starting the Unit in Cooling
Mode
N N o o t t e e : : See the section on "Sequence of Operation" for
a description of the cooling operating sequence.
To start the unit in the cooling mode, set the
thermostat system switch to COOL and move the
thermostat COOL indicator to a setting below room
temperature. The condenser fan motor, compressor
and evaporator fan motor will operate automatically.
24
"Determine Unit
O O p p e e r r a a t t i i n n g g P P r r e e s s s s u u r r e e C C h h e e c c k k s s
After the unit has operated in the cooling mode for a
short period of time, install pressure gauges on the
gauge ports of the discharge and suction line valves
(behind the Compressor access panel). Check the
suction and discharge pressures and compare them to
the normal operating pressures provided in the unit's
SERVICE FACTS.
N N o o t t e e : : Do not use the PRESSURE CURVES from the
unit's SERVICE FACTS to determine the unit
refrigerant charge. The correct charge is shown
on the unit nameplate. To charge the system
accurately, weigh in the charge according to the
unit nameplate and check subcooling against the
Subcooling Charging Table in the SERVICE
FACTS.
V V o o l l t t a a g g e e C C h h e e c c k k
With the compressor operating, check the line voltage
at the unit (contactor is located behind the Control/Heat
access panel). The voltage should be within the range
shown on the unit nameplate. If low voltage is
encountered, check the size and length of the supply
line from the main disconnect to the unit. The line may
be undersized for the length of the run.
C C o o o o l l i i n n g g S S h h u u t t D D o o w w n n
At the thermostat, place the system selector to the OFF
position or reset the thermostat to a setting above
room temperature.

Heating Cycle

These units are equipped with a solid-state ignition
control that lights the burners each time the thermostat
calls for heat. The burners are extinguished during the
OFF cycle.
The gas heating section of the unit can be started using
the following procedure:
1. Be sure the thermostat is at its lowest setting and
the power to the unit is off.
a. Turn the main shutoff valve on the gas supply
line ON.
b. Turn or switch the manual valve on the
combination gas valve ON position.
2. Be sure the burner compartment access panel is in
place.
a. Turn on the electrical power to the unit.
b. Turn the thermostat to the highest setting in the
heating cycle.
3. As the thermostat calls for heat, the system cycles
as follows:
a. The combustion blower is energized.
b. The pressure switch is closed.
18-EB41D1-1B-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents