Table 30. Diagnostics — Starter (continued)
Diagnostic
Affects
Name and
Target
Source
Starter Fault Type
Cprsr
II - xy
Starter Fault Type
Cprsr
III - xy
Starter Module
Memory Error
Cprsr
Type 1 - xy
Starter Module
Memory Error
Cprsr
Type 2 - xy
Transition
Complete Input
Cprsr
Opened - xy
Transition
Complete Input
Cprsr
Shorted - xy
Under Voltage
Chiller

Main Processor Diagnostics

Table 31. Diagnostics — main processor
Diagnostic
Affects Target
Name
AFD Comm Loss
Cprsr
- xA
AFD Failure to
Cprsr
Arm or Start - xA
AC-SVX003A-EN
Severity
Persistence
Immediate
Latch
Immediate
Latch
Warning
Latch
Immediate
Latch
Immediate
Latch
Immediate
Latch
Normal
NonLatch
Severity
Persistence
Immediate
NonLatch
Immediate
Latch
Active Modes
[Inactive
Modes]
a. This is a specific starter test where the Shorting
Contactor (1K3) is individually energized and a check is
made to ensure that there are no currents detected by the
Starting - All
CT's. If current is detected when only S is energized at
types of starters
Start, then 1M is shorted. b. This test in a. above applies to
all forms of starters (Note: It is understood that many
starters do not connect to the Shorting Contactor.).
As part of the normal start sequence to apply power to the
Starting
compressor, the Shorting Contactor (1K3) and then the
[Adaptive
Main Contactor (1K1) were energized. 1.6 seconds later
Frequency
there were no currents detected by the CT's for the last 1.2
Starter Type]
Seconds on all three phases. The test above applies to all
forms of starters except Adaptive Frequency Drives.
Checksum on RAM copy of the Starter LLID configuration
All
failed. Configuration recalled from EEPROM.
Checksum on EEPROM copy of the Starter LLID
All
configuration failed. Default configuration loaded into RAM
and EEPROM.
The Transition Complete input was found to be shorted
All Running
before the compressor was started. This is active for all
Modes
electromechanical starters.
The Transition Complete input was found to be shorted
Pre-Start
before the compressor was started. This is active for all
electromechanical starters.
Pre-Start and
Nom. trip: 60 seconds at less than 87.5%, +/- 2.8% at 200V
Any Ckt(s)
+/- 1.8% at 575V, Auto Reset at 90% or greater for 10
Energized
continuous seconds.
Active Modes
[Inactive
Modes]
Communication has been lost between the UC800 and the
applicable AFD. Once triggered, this diagnostic will auto-
reset after 10 continuous minutes of restored
communication to the compressor. (Note: The timer only
All
starts once communication to the compressor is restored,
which the UC800 will detect. If a manual reset request
occurs during the timer period, it shall reset the diagnostic
and the 'auto-reset' function will then be bypassed.)
The AFD failed to start within the allotted time (1 min).
Definition of the "starting" value is the running status of the
Running
AFD. Note: This is a Controller diagnostic, not one
originating from the AFD.
Diagnostics
Criteria
Criteria
Reset
Level
Local
Local
Local
Local
Local
Local
Remote
Reset
Level
Local
103