9 Program-Mode
9.1 Notes for Program-Mode
9
Program-Mode
Program menus provide specific Flame Scanner tuning values that define response
times and limits.
A complete list of the Program-Mode functions, their defaults, and available selections
are found in
9.1
Notes for Program-Mode
–
The values displayed or changed only apply to the currently selected Tuning
Function-Set. The Channel and Tuning Function-Set selected are displayed in the
upper right corner of the LCD display.
–
To enter Program-Mode, press the RIGHT pushbutton momentarily, followed by the
▼ touch-button within two seconds.
–
Exit the Program-Mode by holding in the d touch-button for two seconds. If there is
no activity for 20 seconds, the SF910i will automatically transfer to Normal-Mode.
–
The menu screens that the user see may vary depending on the configuration.
–
The user cannot directly pass from Program-Mode to Configuration-Mode or
vice-versa. The user must first go to Normal-Mode, then to Configuration-Mode.
–
Recommended initial settings for specific applications can be found in
–
Invalid input out of range as rules in
value is un-changed which can be verified through re-entering and double-checking.
The specific Program-Mode functions are described in the following sections in the order
of their appearance on the menu.
When the user adjust the tuning value through the ▲ touch-button and ▼
touch-button, press the LEFT pushbutton to cancel, and press the RIGHT pushbutton
to confirm that the set value is effective and save.