B Proposed Initial Setting
B.1 Corner Applications

Appendix B Proposed Initial Setting

Notes on the Proposed Initial Settings
Important values for flame detection that must be set before initial start-up are shown in
bold.
Other values that can be changed, but are not critical for flame detection are shown in
plain text.
Using Flame Explorer tool, the user can load from a file the predefined and default
values for a wide range of standard applications. Refer to SF910i Flame Explorer
User Manual (8VZZ005308) for details, and for a list of the pre-defined configurations
that are available.
For safety reasons, the user is requested to prove the Flame Failure Response
Time (FFRT) of the SF910i under any burner load/fuel conditions and under any
selected file of parameters. For EN298 application, the user need to set the DELAY
DROPOUT parameter to <= 0.9s to fulfill the requirement of EN 298 that the FFRT
shall not exceed one second. If there are further adjustments of the flame detector
(DELAY DROPOUT), do not cause the time to rise above one second.
B.1

Corner Applications

Table B.1: Proposed Initial Settings for Corner Applications
Application
Description
Flame Sensor Type
Fuel/Load Switching
Application Select
Hi Limits
AC Amplitude
8VZZ005286 B
Tangential-Coal
w/oil Warm-up
Tangential-Coal
Discriminate
Visible Light Fiber
Visible Light
Optic Scanner
Fiber Optic
Scanner
On
Off
Corner
Corner
Off
Off
Off
Off
Tangential-Gas
Tangential-Oil
only
only
UV Fiber Optic
Visible Light
Scanner
Fiber Optic
Scanner
Off
On
Corner
Corner
Off
Off
Off
Off
Tangential-Gas
and Oil
VL or UV Fibre
Optic Scanner
On
Corner
Off
Off
137