Ao Output; Load Default Parameters; Communication - ABB Uvisor SF910i User Manual

Integrated safeflame scanner
Table of Contents

Advertisement

8 Configuration-Mode
8.3 Configuration Menu Descriptions
Channel Identifiers
Unit ID
Elevation ID
Burner/Combustor/Corner/Lighter ID
The term displayed by the menu will change with "Operation-Mode" selected.
8.3.4

AO Output

Use the Analog Output function to specify the type of information that will be transmitted
to the 4 to 20 analog output. This information can be related to:
Intensity - This option will output the intensity value in a range of 4 to 20 mA = 0 -
100%.
Frequency - This option outputs the Flicker-Frequency value which is proportional
to the maximum Flicker-Frequency for the application selected.
AC-Amplitude - This option will output the AC-Amplitude in a range of 4 to 20 mA =
0 to 100%.
Quality (default) - This option will output the quality value in a range of 4 to 20 mA
= 0 to 100%.
8.3.5

Load Default Parameters

From the local pushbuttons/display, it is possible to request to the unit to load back its
factory default parameters.
In this way, all the unit parameters will be brought back to the factory default with the
following exception, the active protocol will NOT change.
If the unit is MODBUS, it will remain MODBUS (but will bring back address and baud
rate to 1/38.400).
8.3.6

Communication

Use this function to enter the communication protocol type, addresses, and baud rates
for the serial outputs.
8VZZ005286 B
For corner applications: 4 to 20 ma = 0 - 125 Hz
For wall/industrial applications: 4 to 20 ma = 0 - 125 Hz
For lighter applications: 4 to 20 ma = 0 - 125 Hz
For gas turbines: 4 to 20 ma = 0 -125 Hz or 0 - 250 Hz
71

Advertisement

Table of Contents
loading

Table of Contents