6 Operational-Modes

6.2 Normal-Mode

To exit from this mode, the user must configure (either using the Flame Explorer tool or
locally with touch-buttons) the SF910i.
SF910i, when used with its communication line(s) in a bus architecture, needs a
basic configuration to be done before installation. This basic configuration consists
in the selection of the serial line communication protocol and the assignment of the
station address.
These selections must be done manually with the rear cover open and while the
unit is powered. Therefore, in case the unit is to be installed in a hazardous area,
these initial settings cannot be performed on the final location. The unit protocol and
address must be selected before to the actual physical installation, operating on a
lab bench in a non-hazardous area. The initial basic configuration requires connection
to a 24V
6.2
Normal-Mode
Normal monitoring of the flame. In this mode, the flame live data view is only available.
No new parameters can be entered (password protected).
6.3

Configuration-Mode

Configuration of the SF910i unit and its relays. Configuration-Mode can be entered:
Remotely using the Flame Explorer SW Tool (running on a system connected through
the serial line), and this is optional.
Locally by the four touch-buttons on ATB.
8VZZ005286 B
power supply only.
DC
62