5121835-TIM-J-1118
ZKT06 through T12 high static motor - without powered convenience outlet
Compressors
(each)
Size
Volt
(tons)
RLA LRA
MCC
208
13.5
88.0
21.1
230
13.5
88.0
21.1
T06
(6.5)
460
6.0
44.0
9.3
575
4.9
34.0
7.7
208
13.1
83.1
20.5
230
13.1
83.1
20.5
T07
(7.5)
460
6.1
41.0
9.5
575
4.4
33.0
6.8
208
14.5
98.0
22.6
230
14.5
98.0
22.6
T08
(8.5)
460
6.3
55.0
9.9
575
6.0
41.0
9.4
22
OD fan
Supply
Pwr
Pwr exh
motors
blower
conv
motor
(each)
motor
outlet
FLA
FLA
FLA
FLA
2.1
6.8
5.5
0.0
2.1
6.8
5.5
0.0
1.3
3.4
2.2
0.0
0.7
2.4
1.8
0.0
2.1
9.6
5.5
0.0
2.1
9.6
5.5
0.0
1.3
4.7
2.2
0.0
0.7
3.6
1.8
0.0
2.1
9.6
5.5
0.0
2.1
9.6
5.5
0.0
1.3
4.7
2.2
0.0
0.7
3.6
1.8
0.0
Electric heat option
Model
kW
Stages Amps
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
1
MCA
Max fuse
1
MCA
with pwr
breaker
(amps)
exh (amps)
size (amps)
41.4
46.9
50
41.4
46.9
50
55.3
62.2
60
71.0
77.8
80
97.0
103.9
100
41.4
46.9
50
41.4
46.9
50
62.6
69.5
70
80.7
87.5
90
110.7
117.6
125
19.4
21.6
25
19.4
21.6
25
31.3
34.1
35
40.3
43.1
45
55.4
58.1
60
14.7
16.5
15
14.7
16.5
15
24.7
26.9
25
31.9
34.1
35
43.9
46.1
45
43.3
48.8
50
43.3
48.8
50
58.8
65.7
60
74.5
81.3
80
100.5
107.4
110
43.3
48.8
50
43.3
48.8
50
66.1
73.0
70
84.2
91.0
90
114.2
121.1
125
20.9
23.1
25
20.9
23.1
25
32.9
35.7
35
42.0
44.7
45
57.0
59.7
60
14.8
16.6
15
15.3
17.6
20
26.2
28.4
30
33.4
35.6
35
45.4
47.6
50
46.4
51.9
60
46.4
51.9
60
58.8
65.7
60
74.5
81.3
80
100.5
107.4
110
46.4
51.9
60
46.4
51.9
60
66.1
73.0
70
84.2
91.0
90
114.2
121.1
125
21.4
23.6
25
21.4
23.6
25
32.9
35.7
35
42.0
44.7
45
57.0
59.7
60
18.4
20.2
20
18.4
20.2
20
26.2
28.4
30
33.4
35.6
35
45.4
47.6
50
Johnson Controls Ducted Systems
2
Max fuse
/
3
2
/
breaker
3
size with
pwr exh
(amps)
60
60
70
80
110
60
60
70
90
125
25
25
35
45
60
20
20
30
35
50
60
60
70
90
110
60
60
80
100
125
25
25
40
45
60
20
20
30
40
50
60
60
70
90
110
60
60
80
100
125
25
25
40
45
60
25
25
30
40
50