York ZKT06 Installation Manual page 24

Table of Contents

Advertisement

5121835-TIM-J-1118
ZKT06 through T12 standard motor - with powered convenience outlet
Compressors
(each)
Size
Volt
(tons)
RLA LRA
MCC
208
13.5
88.0
21.1
230
13.5
88.0
21.1
T06
(6.5)
460
6.0
44.0
9.3
575
4.9
34.0
7.7
208
13.1
83.1
20.5
230
13.1
83.1
20.5
T07
(7.5)
460
6.1
41.0
9.5
575
4.4
33.0
6.8
208
14.5
98.0
22.6
230
14.5
98.0
22.6
T08
(8.5)
460
6.3
55.0
9.9
575
6.0
41.0
9.4
24
OD fan
Supply
Pwr
Pwr exh
motors
blower
conv
motor
(each)
motor
outlet
FLA
FLA
FLA
FLA
2.1
5.2
5.5
10.0
2.1
5.2
5.5
10.0
1.3
2.6
2.2
5.0
0.7
2.0
1.8
4.0
2.1
5.2
5.5
10.0
2.1
5.2
5.5
10.0
1.3
2.6
2.2
5.0
0.7
2.0
1.8
4.0
2.1
6.8
5.5
10.0
2.1
6.8
5.5
10.0
1.3
3.4
2.2
5.0
0.7
2.4
1.8
4.0
Electric heat option
Model
kW
Stages Amps
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
1
MCA
Max fuse
1
MCA
with pwr
breaker
(amps)
exh (amps)
size (amps)
49.8
55.3
60
49.8
55.3
60
65.8
72.7
70
81.5
88.3
90
107.5
114.4
110
49.8
55.3
60
49.8
55.3
60
73.1
80.0
80
91.2
98.0
100
121.2
128.1
125
23.6
25.8
25
23.6
25.8
25
36.6
39.3
40
45.6
48.3
50
60.6
63.4
70
18.3
20.1
20
18.3
20.6
20
29.2
31.4
30
36.4
38.6
40
48.4
50.6
50
48.9
54.4
60
48.9
54.4
60
65.8
72.7
70
81.5
88.3
90
107.5
114.4
110
48.9
54.4
60
48.9
54.4
60
73.1
80.0
80
91.2
98.0
100
121.2
128.1
125
23.8
26.0
25
23.8
26.0
25
36.6
39.3
40
45.6
48.3
50
60.6
63.4
70
17.2
19.0
20
18.3
20.6
20
29.2
31.4
30
36.4
38.6
40
48.4
50.6
50
53.6
59.1
60
53.6
59.1
60
67.8
74.7
70
83.5
90.3
90
109.5
116.4
110
53.6
59.1
60
53.6
59.1
60
75.1
82.0
80
93.2
100.0
100
123.2
130.1
125
25.1
27.3
30
25.1
27.3
30
37.6
40.3
40
46.6
49.3
50
61.6
64.4
70
21.2
23.0
25
21.2
23.0
25
29.7
31.9
30
36.9
39.1
40
48.9
51.1
50
Johnson Controls Ducted Systems
2
Max fuse
/
3
2
/
breaker
3
size with
pwr exh
(amps)
60
60
80
90
125
60
60
80
100
150
30
30
40
50
70
25
25
35
40
60
60
60
80
90
125
60
60
80
100
150
30
30
40
50
70
20
25
35
40
60
70
70
80
100
125
70
70
90
100
150
30
30
45
50
70
25
25
35
40
60